Figure 3-13 Installation of Single or Parallel Conductor Sets
Although a neutral terminal is available, a neutral conductor is not required for inverter operation. The neutral
terminal is bonded to chassis and only used for voltage sensing. If a neutral conductor is installed, torque the
neutral terminal based on the conductor size according to Table 3-3 using either 3/16 Allen hex key or a slot
torque driver.
Table 3-3 Neutral Lug Torque Specifications
Conductor Size
4 AWG (Cu)
(42.3 mm
2
)
2-1/0 AWG (Cu or Al)
(42.4 to 53.5 mm
2
)
Torque
50 in-lbs
(5.6 N-m)
55 in-lbs
(6.2 N-m)