TOEP C730600 0EA Modbus TCP/IP Installation Manual
43
■
Option Connection Diagram
Figure 5.28 Option Connection Diagram
*1
Connect the specified ground wire for installations on 1000-series, GA500, and HV600 drives. The ground
wire is not necessary for installation on GA700 or GA800 drives.
■
Prepare and Connect Communication Cable Wiring
The option modular connector CN1 port 1 and port 2 act as a switch to allow for
flexibility in cabling topology. Users may employ a traditional star network topology
using either CN1 port 1 or CN1 port 2 on the option. Alternatively, a daisy-chained
approach may be employed by using both CN1 port 1 and CN1 port 2. The daisy-chained
approach reduces the requirements of switch ports. A ring topology is also possible. RSTP
is available to be used in a ring topology.