9 Rapid Spanning Tree Protocol (RSTP)
YASKAWA
TOEP C730600 0EA Modbus TCP/IP Installation Manual
73
1.
Use the keypad to read the IP address values from monitors
U6-80
,
U6-81
,
U6-
82
, and
U6-83
.
The IP address of the option is necessary to access the webpage.
The IP address of the option is necessary to access the webpage. Use the
operator to read the IP address values from monitors
U6-80
,
U6-81
,
U6-82
, and
U6-83
.
Refer to
for example values of the monitors for an option IP address of
192.168.1.20.
Table 9.1 Example IP Address Monitor Values
Monitor
Value
U6-80
192
U6-81
168
U6-82
1
U6-83
20
2.
Enter the IP address to address bar of your web browser (Ex. http://192.168.1.20)
and press the Enter key.
The Home page will be loaded. Refer to
for more information about the
Home page.
3.
Click [Ring] tab on top of the webpage.
The Ring page is displayed with the [Ring Protocol] label in the [RSTP] field set to
[DISABLED].
4.
After changing the setting value of the [Ring Protocol] label to [ENABLED], click
[Save Changes].
The Ring page is automatically updated and RSTP is enabled.
Figure 9.1 Ring Page View