Register Number
(Hex.)
Description
0005
Torque compensation (0.1% signed)
0006
PID setpoint (0.01% signed)
0007
Multi-Function Analog Output Terminal 1 Setting (10 V / 4000 (Hex.))
0008
Multi-Function Analog Output Terminal 2 Setting (10 V / 4000 (Hex.))
0009
MFDO setting
bit 0
Multi-Function Contact Output 1
Terminal M1-M2 (varies by drive model)
bit 1
Multi-Function Contact Output 2
Terminal M3-M4 (varies by drive model)
bit 2
Multi-Function Contact Output 3
Terminal M5-M6 (varies by drive model)
bit 3- 5
Reserved
bit 6
Enables the function in bit 7
bit 7
Fault Relay Output
Terminal MA/MB-MC (varies by drive model)
bit 8 - F
Reserved
000A
Pulse train output (Units: 1/1 Hz, setting range: 0 - 32000)
000B - 000E
Reserved
000F
Command selection setting
bit 0
Reserved
bit 1
Input for the PID setpoint
bit 2
Torque reference/torque limit input (enables the setting
from MEMOBUS/Modbus)
bit 3
Torque compensation input (enables the setting from
MEMOBUS/Modbus)
bit 4 - B
Reserved
bit C
Terminal S5 input of broadcast message
bit D
Terminal S6 input of broadcast message
bit E
Terminal S7 input of broadcast message