60
YASKAWA
TOEP C730600 0EA Modbus TCP/IP Installation Manual
◆
Enter Command Function Differences Depending on the Setting of H5-11
Table 7.5 Enter Command Function Differences Depending on the Setting of H5-11
H5-11 Settings
H5-11 = 0
H5-11 = 1
Time when the
parameter settings
are enabled
When the drive receives the Enter command
from the master
When you change the parameter settings
Upper and lower
limit check
Checks the upper and lower limits and
considers the related parameter settings.
Checks the upper and lower limit of the
changed parameter only.
Default setting of
related parameters
Not affected. The settings of related
parameters remain unchanged. They must be
changed manually, if needed.
Automatically changes the default settings
for the related parameters.
Fault detection when
you set more than
one parameter
Accepts and responds as usual to correct
setting data if the data contains parameter
setting errors. The drive discards the
disabled setting data, but will not return an
error message.
Error occurs if only one setting is invalid.
All data sent are discarded. The drive
discards the data that was sent.
8
Web Interface
The option contains a series of web pages that allow for viewing of status and diagnostic
information through a standard web browser.
The web page is accessed through a self-contained web server at port 80. Access the home
page by typing the IP address of the option in a web browser. Example: "http://
192.168.1.20
”
The IP address of the option can be read using monitors
U6-80 to U6-83
on the digital
operator if it is unknown. Refer to
for more information.
•
Home Page
•
Modbus-TCP page
•
Network Page
•
Ring Page
•
Chart Page
•
Email Alerts Page
•
Parameter Access Page
•
Settings Page
*1
A valid password is necessary to access.
◆
Home Page
The Home page shows the status of the drive and the I/O. It also shows identifying
information about the drive and the option.