4.4.2.3 Protect Parameters
In this interface you can change the Protect parameters of grid voltage, frequency
and recovery, etc., as shown in Figure 4-10. But you can’t enable/disable the function.
The protect parameters are shown in Table 4.3.
Voltage Moving Average
P6/7
MaxTripT(S)
VolMax
MinTripT(S)
VolMin
600.00
88.00%
600.00
110.00%
Grid Over Voltage Protection
VolMaxTripT1(S)
GridVolMax1
P1/7
VolMaxTripT2(S)
GridVolMax2
VolMaxTripT3(S)
GridVolMax3
0.16
120.00%
1.00
110.00%
0.16
120.00%
Grid Low Voltage Protection
P2/7
VolMinTripT1(S)
GridVolMin1
VolMinTripT2(S)
GridVolMin2
VolMinTripT3(S)
GridVolMin3
1.00
60.00%
2.00
88.00%
0.16
45.00%
Grid Low Frequency Protection
P4/7
FrqMinTripT1(S)
GridFrqMin1(Hz)
GridMinTripT2(S)
GridFrqMin2(Hz)
FrqMinTripT3(S)
GridFrqMin3(Hz)
0.16
57.0
2.00
59.5
0.16
57.0
Grid Recovery
P5/7
VolMin
VolMax
FrqMax(Hz)
VolRecoveryT(S)
FrqRecoveryT(S)
FrqMin(Hz)
60.3
300.00
90.00%
107.92%
300.00
59.8
Enable
Disable
Disable
Grid Voltage Balance
P7/7
GridVolBalance
10.00%
Disable
Enable
Disable
Enable
Enable
Enable
Grid Over Frequency Protection
P3/7
FrqMaxTripT1(S)
GridFrqMax1(Hz)
GridMaxTripT2(S)
GridFrqMax2(Hz)
FrqMaxTripT3(S)
GridFrqMax3(Hz)
0.16
62
2.00
60.5
0.16
Enable
Enable
Disable
Disable
Enable
Enable
62
LVRT/HVRT Setup
Setting
P1/2
System Parameters
Protection Parameters
Power Derating Setup
Reactive Power Derating Setup
ARC Parameters
Control Command
Figure 4.10 Protection Parameters Setting
REMARK:
Switching between parameters is done by pressing
and
. Then
press “ENT” to select it, change the parameter value by pressing
and
then press “ENT” to send the parameter to inverter. The LCD will display new
parameters if the setting is successful. Otherwise the old parameters will display on
the LCD.