NOTE 2:
When the ambient temperature is higher than 113°F (45°C), the output
power may begin derating. For DC voltage as shown in Figure 7.3:
Figure 7.3 - PVI 50/60TL Derating Curve with High Temperature
Note:
At 60 degrees C the inverter is likely to shutoff.
Depending on various factors like
angle of installation, air flow and others, the thermal shutdown may occur at higher
temperature like 61-63 degrees C. For designing and modelling purposes one should
consider shut down at 60 degrees C.
Output
Power
Celsius