PVI 50/60 TL Installation and Operation Manual (Rev C)
DOCR-070645-E
Page 44 of 102
(4) The Grid connection type should be (L1, L2, L3, N, PE). A dedicated Neutral wire is
required for proper internal voltage balance.
Either a 3-pole or 4-pole AC circuit breaker should be selected as per the following
specifications.
Choosing any other breaker size may result in nuisance tripping or
rejection from the AHJ.
Table 2.12 - Breaker Values
Inverter
AC breaker rated current
(
A
)
PVI 50TL
80
PVI 60TL
100
NOTE:
If you are using aluminum wires you need to follow the following steps to prep
each cable prior to connecting to the AC terminal block:
a) Using a utility knife, gently strip the top layer of the aluminum conductors
Figure 2-38 Preparing aluminum wires prior to connecting
b) After removing the oxidized layer immediately apply neutral grease (Noalox or acid-
and alkali-free Vaseline) and connect the cable immediately to the terminal. Perform
one cable at a time. If you need to stop the process before applying the grease, and
continue later- you will need to scrape it again. It takes 30-60 seconds for an oxidized
layer to form on top of the conductors.
Acceptable transformer configurations: