Table A.5 Power Ratings Continued
Item
Specification
CIMR-V
o
4A
0011
0018
0023
0031
0038
Maximum Applicable Motor
Capacity (HP)
ND Rating
7.5
10.0
15.0
20.0
25.0
HD Rating
5.0
10.0
10.0
15.0
20.0
Input Input Current (A)
ND Rating
14.0
20.0
24.0
38.0
44.0
HD Rating
10.4
15.0
20.0
29.0
39.0
Output
Output Current (kVA)
8.5
13.3
17.5
23.6
29.0
HD Rating
7.0
11.3
13.7
18.3
23.6
Output Current (A)
11.1
17.5
23.0
31.0
38.0
HD Rating
9.2
14.8
18.0
24.0
31.0
Overload Tolerance
ND Rating: 120% of rated output current for 60 s
HD Rating: 150% of rated output current for 60 s
(Derating may be required for applications that start and stop
frequently)
Carrier Frequency
User-adjustable 2 to 15 kHz
Maximum Output Voltage (V)
Three-phase: 380 to 480 V (proportional to input voltage)
Maximum Output Frequency (Hz)
400 Hz (user-adjustable)
Power
Supply
Rated Voltage Rated Frequency
Three-phase: 380 to 480 V 50/60 Hz
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±5%
Harmonic Corrective Actions DC Link Choke
Optional
<1>
<2>
<3>
Rated motor capacity is calculated with a rated output voltage of 440 V.
<4>
<5>
A.3 Three-Phase 400 V Class Drives
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide
161
A
Specifications