n
Carrier Frequency Selection: C6-02
Fixed Carrier Frequencies
The carrier frequency can be set using parameter C6-02 as shown in table below.
Parameter
Name
Description
Setting Range
Default
C6-02
Carrier
Frequency
Selection
1 : 2.0 kHz
2 : 5.0 kHz
3 : 8.0 kHz
4 : 10.0 kHz
5 : 12.5 kHz
6 : 15.0 kHz
7: Swing PWM 1
8: Swing PWM 2
9: Swing PWM 3
A: Swing PWM 4
B: Leakage Current Rejection PWM
F : User defined (C6-03 to C6-05)
1 to B, F
Determined by
A1-02 and
o2-04.
Reset when
C6-01 is
changed.
<1>
Note:
1.
Swing PWM uses 2.0 kHz carrier frequency as a base. Applying special PWM patterns minimizes
the audible noise of the motor.
2.
The upper limit for the carrier frequency is determined by drive capacity.
u
Drive Input Voltage Setting: E1-01
Set E1-01 according to the power supply voltage. This setting serves as a base value for certain
drive protective functions.
NOTICE: Set drive input voltage (not motor voltage) in parameter E1-01 for proper function of the protective
features of the drive. Failure to comply could result in improper drive operation. Set parameter E1-01 to match
the input voltage of the drive.
Parameter
Name
Description
Setting Range
Default
E1-01
Input
Voltage
Setting
Set to the nominal voltage of the incoming line. Sets
the maximum and base voltage used by preset V/f
patterns (E1-03), and adjusts the levels of drive
protective features (e.g., overvoltage, braking resistor
level, stall prevention, etc.).
200 V Class: 155 to 255
400 V Class: 310 to 510
230 V
<1>
The default value shown here is for 200 V class drives. Double the value for 400 V class drives.
4.6 Basic Drive Setup Adjustments
112
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide