No.
Name
Description
H1-03
Multi-Function Digital Input Terminal S3 Function Selection
Selects function of terminal S3
H1-04
Multi-Function Digital Input Terminal S4 Function Selection
Selects function of terminal S4
H1-05
Multi-Function Digital Input Terminal S5 Function Selection
Selects function of terminal S5
H1-06
Multi-Function Digital Input Terminal S6 Function Selection
Selects function of terminal S6
H1-07
Multi-Function Digital Input Terminal S7 Function Selection
Selects function of terminal S7
H1 Multi-Function Digital Input Selections
H1-
oo
Setting
Function
Description
0
3-Wire Sequence
Closed: Reverse rotation (only for 3-wire sequence)
1
Local/Remote Selection
Open: Remote, Reference 1 or 2 (b1-01/02 or b1-15/16)
Closed: Local, LED operator is run and reference source
2
External Reference 1/2
Open: Run and frequency reference source 1 (b1-01/02)
Closed: Run and frequency reference source 2 (b1-01/02)
3
Multi-Step Speed Reference 1
Used to select Multi-Step Speeds set in d1-01 to d1-16
4
Multi-Step Speed Reference 2
5
Multi-Step Speed Reference 3
6
Jog Reference Selection
Open: Selected speed reference
Closed: Jog Frequency reference (d1-17). Jog has priority over all other
reference sources.
7
Accel/Decel Time 1
Used to switch between Accel/Decel. Time 1/2
8
Baseblock Command (N.O.)
Open: Normal operation
Closed: No drive output
9
Baseblock Command (N.C.)
Open: No drive output
Closed: Normal operation
A
Accel/Decel Ramp Hold
Closed: The drive pauses during acceleration or deceleration and maintains
the output frequency.
B
Drive Overheat Alarm (oH2)
Closed: Displays an oH2 alarm
C
Terminal A1/A2 Enable
Terminal status differs depending on drive software version.
PRG: 1016 and later:
Open: Analog input selected by H3-14 is disabled.
Closed: Analog input selected by H3-14 is enabled.
PRG: 1015 and earlier:
Open: Analog inputs selected for terminals A1 and A2 are disabled.
Closed: Analog inputs selected for terminals A1 and A2 are enabled.
F
Not used
Select this setting when not using the terminal or when using the terminal
in a pass-through mode.
10
Up Command
Open: Maintains the current frequency reference
Closed: Increases or decreases the current frequency reference
11
Down Command
12
Forward Jog
Closed: Runs forward at the Jog Frequency d1-17.
13
Reverse Jog
Closed: Runs reverse at the Jog Frequency d1-17.
B.1 Parameter Table
182
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide