Step
Display/Result
3.
Press
to give the drive a Run command. RUN will light and
the motor will rotate at 6 Hz.
STOP
Off
On
4.
Ensure the motor is rotating in the correct direction and no faults or
alarms occur.
Motor
Forward
5.
If there is no error in step 4, press
to increase the frequency
reference. Increase the frequency in 10 Hz increments verifying
smooth operation results at all speeds. For each frequency, monitor
the drive output current (U1-03) through the LED operator to confirm
the current is well below the motor rated current. Example: 6 Hz →
60 Hz.
6.
The drive should operate normally. Press
STOP
to stop the motor.
RUN flashes until the motor comes to a complete stop.
STOP
Flashing
Off
4.8 No-Load Operation Test Run
124