5.4
Operator Programming Errors
An Operator Programming Error (oPE) occurs when an inappropriate parameter is set or an
individual parameter setting is inappropriate.
u
oPE Codes, Causes, and Possible Solutions
Table 5.4 oPE Codes, Causes, and Possible Solutions
LED Operator Display
Error Name
oPE01
Drive Capacity Setting Fault
Drive capacity and the value set to o2-04 do not match.
oPE02
Parameter Range Setting Error
Use U1-18 to find parameters set outside the range.
oPE03
Multi-Function Input Selection Error
A contradictory setting is assigned to multi-function
contact inputs H1-01 to H1-07.
oPE04
Initialization required.
oPE05
Run Command/Frequency Reference Source Selection
Error
oPE07
Multi-Function Analog Input Selection Error
A contradictory setting is assigned to multi-function
analog inputs H3-02 through to H3-10 and PID functions
conflict.
oPE08
Parameter Selection Error
A function has been set that cannot be used in the motor
control method selected.
oPE09
PID Control Selection Fault
PID control function selection is incorrect. Requires that
PID control is enabled (b5-01 = 1 to 4).
oPE10
V/f Data Setting Error
The following setting errors have occurred where: E1-04
is greater than or equal to E1-06 is greater than or equal to
E1-07 is greater than or equal to E1-09.
Or the following setting errors have occurred: E3-04 is
greater than or equal to E3-06 is greater than or equal to
E3-07 is greater than or equal to E3-09.
oPE11
Carrier Frequency Setting Error
Correct the setting for the carrier frequency.
oPE13
Pulse Monitor Selection Error
Incorrect setting of monitor selection for Pulse Train
(H6-06).
5.4 Operator Programming Errors
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide
149
5
Troubleshooting