Specifications C - 3
Table C.2 480Vac Drive Specifications
Model Number CIMR-P7U
40P4
40P7
41P5
42P2
43P7
45P5
47P5
4011
4015
4018
Rated output capacity (kVA)
1.4
1.6
2.8
4.0
5.8
9.5
13.0
21.0
26.0
30.0
Motor HP (460V)
0.5/0.75
1
1.5/2
3
5
7.5
10
15/20
25
30
Rated output current (A)
1.8
2.1
3.7
5.3
7.6
12.5
17.0
27.0
34.0
40.0
Max. output voltage (V)
3-phase; 380, 400, 415, 440, 460, or 480Vac (Proportional to input voltage.)
Max. output frequency (Hz)
120 Hz
Rated voltage (V)
Rated frequency (Hz)
3-phase, 380, 400, 415, 440, 460 or 480Vac, 50/60 Hz
Rated input current (A)
2.2
2.5
4.4
6.4
9.0
15
20
33
40
48
Allowable voltage fluctuation
+ 10%, - 15%
Allowable frequency fluctuation
±5%
Measures for
power supply
harmonics
DC Reactor
Optional
12-pulse
Rectification
Not possible
Table C.2 480Vac Drive Specifications (Continued)
Model Number CIMR-P7U
4030
4037
4045
4055
4075
4090
4110
4160
4185
4220
4300
Rated output capacity (kVA)
51.0
59.0
73.0
95.0
120.0
140.0
180.0
230.0
315.0
390.0
510.0
Motor HP (460V)
40/50
60
75
100
125
150
200
250
300/350
400/450
500+
Rated output current (A)
67.2
77.0
96.0
125.0
156.0
180.0
240.0
304.0
414.0
515.0
675.0
Max. output voltage (V)
3-phase, 380, 400, 415, 440, 460 or 480Vac (Proportional to input voltage)
Max. output frequency (Hz)
120 Hz
Max. voltage (V)
Rated frequency (Hz)
3-phase, 380, 400, 415, 440, 460, or 480Vac, 50/60 Hz
Rated input current (A)
74
85
106
134
172
198
264
334
456
567
743
Allowable voltage fluctuation
+ 10%, - 15%
Allowable frequency fluctuation
±5%
Measures for
power supply
harmonics
DC Reactor
Built-in
12-Pulse
Rectification
Possible
Note: The maximum applicable motor output is given for a standard 4-pole motor. When selecting the actual motor and Drive, be sure that the Drive's
rated output current is applicable for the motor's rated current.
A 3-wire phase-shifting transformer is required on the power supply for 12-pulse rectification.
O
ut
put r
at
ing
s
Power
s
upp
ly c
h
ar
act
er
ist
ics
Cont
ro
l
char
act
er
is
ti
cs
O
utput r
at
ings
Power
s
upp
ly c
h
ar
act
er
ist
ics
C
ontr
o
l
ch
ar
act
er
ist
ics
Summary of Contents for P7
Page 1: ...P7 Drive User Manual Model P7U Document Number TM P7 01...
Page 58: ...Electrical Installation 2 30...
Page 74: ...Digital Operator 3 16...
Page 84: ...Start Up 4 10 Notes...
Page 144: ...Programming 5 60 Notes...
Page 210: ...Capacity Related Parameters B 6 Notes...
Page 238: ...Spare Parts F 4 Notes...
Page 244: ...EMC Compatibility G 6 Notes...