Diagnostic & Troubleshooting 6 - 5
OH1
Heatsnk MAX Temp
Cooling Fin/Cooling Fin Fan Overheat
The temperature of the Drive cooling fin
exceeded the temperature programmed in
parameter L8-02
Cooling fan(s) are not
working, high ambient
temperature, a heat source is
too close to the Drive
Check for dirt build-up on the
fans and cooling fins
Reduce the ambient temperature
around the Drive
Drive Internal Cooling Fan
Remove the heating unit
OH3
Motor Overheat 1
Motor Overheating Alarm
The Drive stops or continues operation
according to the setting of L1-03.
Overheating of motor as
measured by motor thermistor
Recheck the cycle time and the
size of the load
Recheck the accel/decel time
(C1-01 and C1-02)
Recheck the V/F pattern (E1-01
thru E1-13)
Recheck the motor rated current
value (E2-01)
OH4
Motor Overheat 2
Motor Overheating Fault
The Drive stops operation according to the
setting of L1-04.
Overheating of motor as
measured by motor thermistor
Recheck the cycle time and the
size of the load
Recheck the accel/decel time
(C1-01 and C1-02)
Recheck the V/F pattern (E1-01
thru E1-13)
Recheck the motor rated current
value (E2-01)
OL1
Motor Overloaded
Motor Overload
Designed to protect the motor.
Fully adjustable from parameter E2-01
The load is too large. The
cycle time is too short at the
accel/decel time
Recheck the cycle time and the
size of the load as well as the
times set in C1-01 and C1-02
The voltage of the V/F pattern
is high
Review the V/F pattern
parameters, E1-01 thru E1-13
Motor rated current setting is
improper
Check the motor rated current
value in E2-01
OL2
Inv Overloaded
Drive Overload
Designed to protect the Drive
The load is too large. The
cycle time is too short at the
accel/decel time
Recheck the cycle time and the
size of the load as well as the
times set in C1-01 and C1-02
The voltage of the V/F pattern
is high
Review the V/F pattern
parameters, E1-01 thru E1-13
The size of the Drive is small
Change to a larger size Drive
OL3
Overtorque Det 1
Overtorque Detection 1
Drive output current > L6-02 for more than
the time set in L6-03
Motor is overloaded
Ensure the values in L6-02 and
L6-03 are appropriate
Check application/machine
status to eliminate fault
OPR
Oper Disconnect
Digital Operator Connection Fault
The Drive will stop if the digital operator is
removed when the Drive is commanded to
run through the digital operator
The digital operator is not
attached or the digital opera-
tor connector is broken
Attach the digital operator
Check the digital operator
connector
Verify the setting of o2-06
Table 6.1 Fault Displays and Processing
Digital
Operator Display
Description
Cause
Corrective Action
Summary of Contents for P7
Page 1: ...P7 Drive User Manual Model P7U Document Number TM P7 01...
Page 58: ...Electrical Installation 2 30...
Page 74: ...Digital Operator 3 16...
Page 84: ...Start Up 4 10 Notes...
Page 144: ...Programming 5 60 Notes...
Page 210: ...Capacity Related Parameters B 6 Notes...
Page 238: ...Spare Parts F 4 Notes...
Page 244: ...EMC Compatibility G 6 Notes...