Parameters A - 11
Motor Setup
E2-01
Motor Rated Current
Motor Rated FLA
Set to the motor nameplate full load amps.
10% to
200% kVA
Dependent
kVA
Dependent
Quick Setting
E2-03
No-Load Current
Sets the magnetizing current of the motor.
kVA
Dependent
kVA
Dependent
Programming
E2-05
Motor Line-to-Line
Resistance
Term Resistance
Phase to phase motor resistance, normally set by the autotuning
routine.
0.000 to
65.000
kVA
Dependent
Programming
Com OPT Setup
F6-01
Operation Selection after
Communication Error
Comm Bus Flt Sel
Sets the stopping method for option PCB communications error
(BUS fault). Active only when a communications option PCB is
installed and when b1-01 or b1-02 = 3.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
0 to 3
1
Quick Setting
F6-02
Detection Selection of
External Fault from
Communication Option Card
EF0 Detection
0: Always detected
1: Detected only during operation
0 or 1
0
Programming
F6-03
Stopping Method for
External Fault from
Communication Option Card
EF0 Fault Action
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
0 to 3
1
Programming
F6-05
Current Monitor Display Unit
Selection
Current Unit Sel
0: A Display (Amps)
1: 100%/8192 (Drive Rated Current)
0 or 1
0
Programming
Table 1: Parameter List (Continued)
Parameter
No.
Parameter Name
Digital Operator Display
Description
Setting
Range
Factory
Setting
Menu
Location
Summary of Contents for P7
Page 1: ...P7 Drive User Manual Model P7U Document Number TM P7 01...
Page 58: ...Electrical Installation 2 30...
Page 74: ...Digital Operator 3 16...
Page 84: ...Start Up 4 10 Notes...
Page 144: ...Programming 5 60 Notes...
Page 210: ...Capacity Related Parameters B 6 Notes...
Page 238: ...Spare Parts F 4 Notes...
Page 244: ...EMC Compatibility G 6 Notes...