Specifications C - 2
Standard Drive Specifications
The standard Drive specifications are listed in the following tables.
!
208-240Vac
Table C.1 208-240Vac Drive Specifications
Model Number CIMR-P7U
20P4
20P7
21P5
22P2
23P7
25P5
27P5
2011
2015
2018
2022
2030
Rated output capacity (kVA)
1.4
1.8
3.0
4.1
6.4
8.8
12.0
18.0
23.0
29.0
34.0
44.0
Motor HP
208V
0.5/0.75
1
1.5/2
3
5
7.5
10
15
20
25
30
40
230V
0.5/0.75
1
1.5/2
3
5
7.5
10
15
20
25
30
40
Rated output current (A)
3.6
4.6
7.8
10.8
16.8
23.0
31.0
46.2
59.4
74.8
88.0
115.0
Max. output voltage (V)
3-phase; 200, 208, 220, 230, or 240Vac (Proportional to input voltage)
Max. output frequency (Hz)
120 Hz
Rated voltage (V)
Rated frequency (Hz)
3-phase, 200/208/220/230/240Vac, 50/60 Hz
Rated input current (A)
4.3
5.5
9.4
13
20
24
37
53
70
89
98
120
Allowable voltage fluctuation
+ 10%, - 15%
Allowable frequency fluctuation
±5%
Measures for
power supply
harmonics
DC Reactor
Optional
Built-in
12-Pulse
Rectification
Not possible
Possible
Note: The maximum applicable motor output is given for a standard 4-pole motor. When selecting the actual motor and Drive, be sure that the Drive's
rated output current is applicable for the motor's rated current.
A phase-shifting transformer is required on the power supply for 12-pulse rectification.
Table C.1 208-230Vac Drive Specifications (Continued)
Model Number CIMR-P7U
2037
2045
2055
2075
2090
2110
Rated output capacity (kVA)
62.0
73.0
82
120.0
140.0
160.0
Motor HP
208V
50
60
75
100
125
150
230V
50/60
75
-
100/125
-
150
Rated output current (A)
162.0
192.0
215
312.0
360.0
415.0
Max. output voltage (V)
3-phase; 200, 208, 220, 230, or 240Vac
(Proportional to input voltage)
Max. output frequency (Hz)
120 Hz
Rated voltage (V)
Rated frequency (Hz)
3-phase, 200/208/220/230/240Vac, 50/60 Hz
Rated input current (A)
180
212
237
350
396
457
Allowable voltage fluctuation
+ 10%, - 15%
Allowable frequency fluctuation
±5%
Measures for
power supply
harmonics
DC Reactor
Built-in
12-Pulse
Rectification
Possible
Note: The maximum applicable motor output is given for a standard 4-pole motor. When selecting the actual motor and Drive, be sure that the Drive's rated
output current is applicable for the motor's rated current.
A phase-shifting transformer is required on the power supply for 12-pulse rectification.
O
utput r
at
ings
P
o
wer
s
u
pply
c
h
ar
ac
te
ri
st
ic
s
C
ont
ro
l
char
act
er
is
ti
cs
Output r
ati
ngs
C
o
ntr
o
l
char
act
er
is
ti
cs
P
o
wer
s
upply
c
h
ar
act
er
is
ti
cs
Summary of Contents for P7
Page 1: ...P7 Drive User Manual Model P7U Document Number TM P7 01...
Page 58: ...Electrical Installation 2 30...
Page 74: ...Digital Operator 3 16...
Page 84: ...Start Up 4 10 Notes...
Page 144: ...Programming 5 60 Notes...
Page 210: ...Capacity Related Parameters B 6 Notes...
Page 238: ...Spare Parts F 4 Notes...
Page 244: ...EMC Compatibility G 6 Notes...