Deployment CPU iC921xM-FSoE
iC9200 Series
System variables and status information > System variables
System varia-
bles SPLC_CON-
TROL_COMMAND
and SPLC_CON-
TROL_CONFIRM
This bit is set if the safety CPU is in one of the two DEBUG states (DEBUG-RUN
or DEBUG-STOP/DEBUG-HALT). This bit is not set in the SAFE-STOP and SAFE-
RUN states.
■
Bit 7: Warning
–
WARN - The set WARN bit (WARNING) indicates a collective warning message
from the safety CPU.
■
Bit 11 ... 8: reserved
■
Bit 12: Error stack
–
EST - The EST (error stack) bit indicates that diagnostic and error messages are
present from the safety operating system of the safety CPU.
This bit is set if there is at least one entry in the error memory of the safety
operating system. These messages can be read and analyzed via iCube Engineer.
As soon as the error memory was read via iCube Engineer and thus cleared, this
bit is automatically reset.
■
Bit 13: reserved
■
Bit 14: POST
–
POST - POWER ON SELF TEST
This bit is set for the duration of the Power-ON-SelbstTest of the safety CPU. After
the self-test is completed, it is reset.
■
Bit 15: Fail safe state
–
FS - Failure State
This bit is set as soon as an error is detected that sets the Safety CPU to the
Fail
Safe
state.
In this state, the corresponding further
error code is contained in the diagnostic parameter registers of the safety CPU
(SPLC.DIAG.PARAM_REG and SPLC.DIAG.PARAM_2_REG).
■
The system variable SPLC_CONTROL_COMMAND is used to request the resetting of
diagnostic values from the non-safety project.
■
Via the system variable SPLC_CONTROL_CONFIRM, the safety CPU confirms in the
non-safety project that the diagnostic values were reset.
SPLC_CONTROL_COMMAND
System variable
Type - description
SPLC_CONTROL_COMMAND
SPLC_CONTROL _TYPE - Data structure with 32 bits for enabling
functions of the safety CPU.
CODE
■
DWORD - Bit 0: Request resetting of the minimum and max-
imum safety round trip times (SRT_MIN, SRT_MAX).
–
Data direction within the Safety CPU: Standard component
à
Safety component
PARAM
■
DWORD - Bit 31 ... 1: Reserved
SPLC_CONTROL_CONFIRM
System variable
Type - description
SPLC_CONTROL_CONFIRM
SPLC_CONTROL _TYPE - Data structure with 32 bits for con-
firming functions of the safety CPU that were requested via the
variable SPLC_CONTROL_COMMAND.
CODE
■
DWORD - Bit 0: Confirmation resetting the minimum and max-
imum safety round trip times (SRT_MIN, SRT_MAX).
–
Data direction within the Safety CPU: Safety component
à
Standard component
PARAM
■
DWORD - Bit 31 ... 1: Reserved