H7: Virtual MFIO selection
No.
(Hex.)
Name
Description
Default
(Range)
H7-00
(116F)
Expert
Virtual MFIO selection
Sets the function to enable and disable the virtual I/O function. Set this parameter to 1 to operate the
virtual I/O function.
0 : Disabled
1 : Enabled
0
(0, 1)
H7-01
(1185)
Expert
Virtual Multi-Function Input
1
Sets the function that enters the virtual input set in
H7-10 [Virtual Multi-Function Output 1]
.
Note:
Settings
1B [Programming Lockout]
and
11B [!Programming Lockout]
are not available.
F
(1 - 1B8)
H7-02
(1186)
Expert
Virtual Multi-Function Input
2
Sets the function that enters the virtual input set in
H7-12 [Virtual Multi-Function Output 2]
.
Note:
Settings
1B [Programming Lockout]
and
11B [!Programming Lockout]
are not available.
F
(1 - 1B8)
H7-03
(1187)
Expert
Virtual Multi-Function Input
3
Sets the function that enters the virtual input set in
H7-14 [Virtual Multi-Function Output 3]
.
Note:
Settings
1B [Programming Lockout]
and
11B [!Programming Lockout]
are not available.
F
(1 - 1B8)
H7-04
(1188)
Expert
Virtual Multi-Function Input
4
Sets the function that enters the virtual input set in
H7-16 [Virtual Multi-Function Output 4]
.
Note:
Settings
1B [Programming Lockout]
and
11B [!Programming Lockout]
are not available.
F
(1 - 1B8)
H7-10
(11A4)
Expert
Virtual Multi-Function
Output 1
Sets the function for virtual digital output 1.
F
(0 - 1A7)
H7-11
(11A5)
Expert
Virtual Output 1 Delay Time Sets the minimum ON time for virtual digital output 1.
0.1 s
(0.0 - 25.0 s)
H7-12
(11A6)
Expert
Virtual Multi-Function
Output 2
Sets the function for virtual digital output 2.
F
(0 - 1A7)
H7-13
(11A7)
Expert
Virtual Output 2 Delay Time Sets the minimum ON time for virtual digital output 2.
0.1 s
(0.0 - 25.0 s)
H7-14
(11A8)
Expert
Virtual Multi-Function
Output 3
Sets the function for virtual digital output 3.
F
(0 - 1A7)
H7-15
(11A9)
Expert
Virtual Output 3 Delay Time Sets the minimum ON time for virtual digital output 3.
0.1 s
(0.0 - 25.0 s)
H7-16
(11AA)
Expert
Virtual Multi-Function
Output 4
Sets the function for virtual digital output 4.
F
(0 - 1A7)
H7-17
(11AB)
Expert
Virtual Output 4 Delay Time Sets the minimum ON time for virtual digital output 4.
0.1 s
(0.0 - 25.0 s)
H7-30
(1177)
Expert
Virtual Analog Input
Selection
Sets the virtual analog input function.
F
(0 - 31)
H7-31
(1178)
RUN
Expert
Virtual Analog Input Gain
Sets the virtual analog input gain.
100.0%
(-999.9 - 999.9%)
H7-32
(1179)
RUN
Expert
Virtual Analog Input Bias
Sets the virtual analog input bias.
0.0%
(-999.9 - 999.9%)
H7-40
(1163)
Virtual Analog Out Signal
Select
Sets the signal level of the virtual analog output.
0 : 0 to 100% (Absolute Value)
1 : -100 to 100%
2 : 0 to 100% (Lower Limit at 0)
0
(0 - 2)