background image

Reactor

Installation

Guide

Performance and Protection for Drives

When installing the KLR/KDR Reactors on

the 

OUTPUT

side  of  the  Variable

Frequency  Drive  (VFD),  please  use  the

following guidelines: 

TCI  recommends  1.5%  impedance

reactors  to  be  used  on  the  output  of  the

VFD.  In the case of the KDR line, use only

the KDR OUTPUT reactors.

Reactors  should  be  mounted  as

close to the output terminals of the VFD as

possible.    

TCI  suggests  that  the  reactor  be

used  in applications where  the  motor  lead

length  is  less  than  100  feet.  For

applications with motor lead lengths greater

than  100  feet,  TCI  offers  KLC/KLCUL

Output  Filters  and  KMG  MotorGuard  High

Performance Sinewave Filters. 

Reactors are sized by the Full Load

Amps located on the motor nameplate.

OUTPUT

Recommendations and Considerations

Please contact TCI Technical Support or your

TCI  distributor  for  application  information

regarding  the  use  of  these  reactors  on  the

load  or  output  side  of  the  VFD,  or  in

applications where inductors are used.

Warnings and Cautions

 

!

General Safety Instructions

 

Warning

Dangerous Voltage Warning: warns of
situations in which a high voltage can
cause physical injury and/or equipment
damage.  The text next to this symbol
describes ways to avoid the danger.

Warning

General Warning: warns of situations
that can cause physical injury and/or
equipment damage by means other
than electrical.  The text next to this
symbol describes ways to avoid the
danger.

 

Warning

 

!

Warning

Be sure to read, understand, and
follow all safety instructions.

 

!

Warning

Only qualified electricians should
carry out all electrical installation and
maintenance work on reactors.

 

!

Warning

All wiring must be in accordance with
the National Electrical Code (NEC)
and/or any other codes that apply to
the installation site.

Disconnect all power before working
on the equipment. Do not attempt any
work on a powered reactor.

 

Warning

The reactor, VFD, motor, and other
connected equipment must be 
properly grounded.

 

Warning

The VFD terminals and connected
cables are at a dangerously high
voltage when power is applied to the
VFD, regardless of motor operation.