TCi KLR Installation Manual Download Page 2

Field Wiring Information

Below is the typical wiring diagram for the 3-phase

reactor  applied  to  the  front  end  of  the  Variable

Frequency Drive (VFD).

Single-phase applications are acceptable,  howev-

er, it is important to size the unit based on the sin-

gle  phase  Full  Load  Amperage  of  the  VFD.  The

input and output connections should be on  termi-

nals A and C to ensure proper performance.

Product Specifications

Wiring Diagram

L

O

A

D

L

IN

E

* For single-phase applications, use coils
A and C. Isolate terminals B1 and B2.

u

3-Phase, 600 Volt Class

u

UL Recognized; File E-116124

u

CE Marked

u

CSA Approved

u

Current rated device

u

200% rated current for 3 minutes

u

Ambient Temperature: 40° C

u

Patented Bobbin Construction on 

units smaller than 110 amps

u

Distributed Gap Technology

TCI recommends that these reactors

be wired as close to the front end of the VFD

as possible.

In  standard  40°  C  ambient  or  less

installations, a clearance of 3 inches on all

sides  of  the  reactors  and  its  enclosure  is

recommended  for  assisting  in  heat

dissipation  and  ample  wire  bending  space.

This  is  a  general  guideline  for  typical

applications.  If the reactor is being installed

next to a heat sensitive instrument or control

device,  we  recommend  reviewing  specific

requirements or heat limitations.  Line reac-

tor  heat  loss  information  is  available  in  the

standard TCI product literature or on the web

at Trans-Coil website.  

These  reactors  are  designed  to  be

floor-mounted,  or  wall-mounted.    Large

open-style  devices  should  be  panel

mounted  by  incorporating  a  bracket  that

would  act  as  a shelf to support the reactor

and/or enclosure.  When installing an open

style  device  in  an  existing  control  cabinet,

drive cabinet, motor control center, or other

large  enclosure,  the  reactor  should  be

mounted in  the  lower  half  of  the  cabinet to

prevent  hot  spots  or  pockets  of  heat.

Locating the reactor in the lower half of the

cabinet  typically  allows  better  thermal

dissipation and heat convection.

The  KLR/KDR  input  line  reactor

should  be  located  as  close  to  the  drive  as

possible  to  have  the  greatest  success  in

both protecting the VFD as well as mitigating

line harmonics.  We recommend this be 10

feet of cable or less.   

KLR/KDR Line Reactor

Installation Instruction

INPUT

Recommendations and Considerations

When installing the KLR/KDR Line Reactors

on  the 

INPUT

side  of  the  Variable

Frequency  Drive  (VFD),  please  use  the

following guidelines when wiring the unit:

The  KLR/KDR  Line  Reactor  is  a  3-

phase device and should be wired in series

and positioned on the input side of the VFD.

All Terminal Block connectors will be

marked.  A1,  B1,  and  C1  are  the  input

terminals  where  the  3  phases  of  incoming

power are to be wired.  As a result, A2, B2,

and C2 are the output terminals.  Units with

copper  bus  or  ring  lug  terminals  are  not

marked.    In  these  cases,  either  the  upper

terminals or the lower terminals can be used

as the input terminals, as long as the selec-

tion is consistent.  For example, if an upper

terminal  is  selected  as  the  input,  all  upper

terminals  must  be  input  terminals.    Wiring

from the output terminals should connect to

the input of the VFD.

Refer  to  NEC  wiring  practices  for

appropriate wire sizes for your application.

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Reviews: