YASKAWA
TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
183
No.
(Hex.)
Name
Description
Default
(Range)
b5-85
(31B3)
RUN
Feedback Loss GoTo Freq
Timeout
When
b5-82 = 3 [Feedback Loss 4
~
20mA Detect Sel = Run At b5-83]
and the Feedback signal is
lost, the drive will run at the
b5-83 [Feedback Loss Goto Frequency]
speed for this length of time,
after which the drive will fault on
FDBKL [WIRE Break]
.
Note:
Set this parameter to 0.0 s to disable the function.
0 s
(0 - 6000 s)
b5-86
(31B4)
RUN
Feedback Loss Start Delay
When you initiate an AUTO Run command, the drive will wait for this length of time before it will
fault on
FDBKL [WIRE Break]
or use parameter
b5-83 [Feedback Loss Goto Frequency]
.
0.0 s
(0.0 - 120.0 s)
◆
b8: Energy Saving
No.
(Hex.)
Name
Description
Default
(Range)
b8-01
(01CC)
Energy Saving Control
Selection
Sets the Energy-saving control function.
0 : Disabled
1 : Enabled
0
(0, 1)
b8-04
(01CF)
Expert
Energy Saving Coefficient
Value
Sets the Energy-saving control coefficient to maintain maximum motor efficiency. The default setting
is for Yaskawa motors.
Note:
The minimum values and the maximum values are different for different drive models.
•
2011 to 2024, 4005 to 4008: 0.0 - 2000.0
•
2031 to 2273, 4011 to 4302: 0.00 - 655.00
Determined by E2-11 and
o2-04
(0.00 - 655.00)
b8-05
(01D0)
Expert
Power Detection Filter Time
Sets the time constant to measure output power.
20 ms
(0 - 2000 ms)
b8-06
(01D1)
Expert
Search Operation Voltage
Limit
Sets the voltage limit for Search Operation as a percentage of the motor rated voltage.
0%
(0 - 100%)