YASKAWA
TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
185
◆
C4: Torque Compensation
No.
(Hex.)
Name
Description
Default
(Range)
C4-01
(0215)
RUN
Torque Compensation Gain
Sets the gain for the torque compensation function. Use this parameter value for motor 1 when you
operate multiple motors.
1.00
(0.00 - 2.50)
C4-02
(0216)
RUN
Torque Compensation Delay
Time
Sets the torque compensation delay time. Usually it is not necessary to change this setting.
200 ms
(0 - 60000 ms)
◆
C6: Carrier Frequency
No.
(Hex.)
Name
Description
Default
(Range)
C6-02
(0224)
Carrier Frequency Selection
Sets the carrier frequency for the transistors in the drive.
1 : 2.0 kHz
2 : 5.0 kHz
3 : 8.0 kHz
4 : 10.0 kHz
5 : 12.5 kHz
7 : Swing PWM1 (Audible Sound 1)
8 : Swing PWM2 (Audible Sound 2)
9 : Swing PWM3 (Audible Sound 3)
A : Swing PWM4 (Audible Sound 4)
B : Leakage Current Rejection PWM
F : User Defined (C6-03 to C6-05)
Note:
•
The carrier frequency for Swing PWM 1 to 4 is equivalent to 2.0 kHz. Swing PWM applies a
special PWM pattern to decrease the audible noise.
•
Setting
B
uses a PWM pattern that decreases the leakage current that the drive detects over long
wiring distances. This can help decrease alarm detection and decrease problems with the current
monitor from leakage current over long wiring distances.
Determined by o2-04
(1 - F)
C6-03
(0225)
Carrier Frequency Upper
Limit
Sets the upper limit of the carrier frequency. Set
C6-02 = F [Carrier Frequency Selection = User
Defined (C6-03 to C6-05)]
to set this parameter.
Determined by C6-02
(1.0 - 12.5 kHz)
C6-04
(0226)
Carrier Frequency Lower
Limit
Sets the lower limit of the carrier frequency. Set
C6-02 = F [Carrier Frequency Selection = User
Defined (C6-03 to C6-05)]
to set this parameter.
Determined by C6-02
(1.0 - 12.5 kHz)
C6-05
(0227)
Carrier Freq Proportional
Gain
Sets the proportional gain for the carrier frequency. Set
C6-02 = F [Carrier Frequency Selection =
User Defined (C6-03 to C6-05)]
to set this parameter.
Determined by C6-02
(0 - 99)