242
YASKAWA
TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
No.
(Hex.)
Name
Description
Default
(Range)
YF-24
(3F67)
RUN
PI Auxiliary Ctrl Maximum
Level
Sets the maximum level for PI Auxiliary Control. When the level is more than this setting for longer
than
YF-05 [PI Aux Control Sleep Delay Time]
, the drive will go to sleep and turn off all lag drives.
Note:
•
Set this parameter to 0.0 to disable the function.
•
Parameters
YF-21 [PI Aux Ctrl Level Unit Selection]
and
YF-22 [PI Aux Level Decimal Place
Pos]
set the unit and resolution.
0.0 PSI
(0.0 - 6000.0 PSI)
YF-25
(3F68)
RUN
PI Aux Control Activation
Level
Sets the level to activate the PI Auxiliary Control.
Note:
•
The drive response changes when the
YF-23 [PI Aux Ctrl Output Level Select]
setting changes.
–
YF-23 = 0 [Direct Acting]
:
When the PI Aux Feedback level is more than this setting for longer than
YF-26 [PI Aux
Control Activation Delay]
, the drive will activate the PI Auxiliary Control to control the
output frequency.
–
YF-23 = 1 [Inverse Acting]
:
When the PI Aux Feedback level is less than this setting for longer than
YF-26
, the drive will
activate PI Auxiliary Control to control the output frequency.
•
When you set this parameter to 0.0 PSI, PI Auxiliary Control is always enabled.
•
Parameters
YF-21 [PI Aux Ctrl Level Unit Selection]
and
YF-22 [PI Aux Level Decimal Place
Pos]
set the unit and resolution.
0.0 PSI
(0.0 - 6000.0 PSI)
YF-26
(3F69)
RUN
PI Aux Control Activation
Delay
Sets the delay time to activate the PI Auxiliary Control.
Note:
•
The drive response changes when the
YF-23 [PI Aux Ctrl Output Level Select]
setting changes.
–
YF-23 = 0 [Direct Acting]
:
When the PI Aux Feedback level is more than
YF-25 [PI Aux Control Activation Level]
for
longer than this time, the drive will activate the PI Auxiliary Control to control the output
frequency.
–
YF-23 = 1 [Inverse Acting]
:
When the PI Aux Feedback level is less than
YF-25
for longer than this time, the drive will
activate PI Auxiliary Control to control the output frequency.
•
When you set this parameter to 0.0 PSI, PI Auxiliary Control is always enabled.
2 s
(0 - 3600 s)
YF-32
(3F6F)
PI Aux Custom Unit
Character 1
Sets the first character of the PI Aux custom unit display when
YF-21 = 49 [PI Aux Ctrl Level Unit
Selection = Custom (YF-32
~
34)]
.
41
(20 - 7A)
YF-33
(3F70)
PI Aux Custom Unit
Character 2
Sets the second character of the PI Aux custom unit display when
YF-21 = 49 [PI Aux Ctrl Level
Unit Selection = Custom (YF-32
~
34)]
.
41
(20 - 7A)
YF-34
(3F71)
PI Aux Custom Unit
Character 3
Sets the third character of the PI Aux custom unit display when
YF-21 = 49 [PI Aux Ctrl Level Unit
Selection = Custom (YF-32
~
34)]
.
41
(20 - 7A)
YF-35
(3F72)
PI Aux Minimum
Transducer Scale
Sets the minimum scale output of the pressure transducer that is connected to the terminal set for
H3-
xx = 27 [MFAI Function Selection = PI Auxiliary Control Feedback]
.
Note:
•
To enable this parameter, set it to less than
YF-02 [PI Aux Control Transducer Scale]
. If you set
it to more than
YF-02
, it will disable the PI Auxiliary Feedback (set to 0).
•
Parameters
YF-21 [PI Aux Ctrl Level Unit Selection]
and
YF-22 [PI Aux Level Decimal Place
Pos]
set the unit and resolution.
0.0 PSI
(-999.9 - +999.9 PSI)