2-10
DIGITAL OPERATOR
DESCRIPTION
KEY SEQUENCE
DISPLAY
Table 2-2. V/f Startup Procedure - Continued
Test run the drive from the
Digital Operator
WARNING: The next key press will cause
the motor to turn! Take appropriate safety
precautions!
Press the
key then slowly turn the
Digital Operator Pot to the right about 1/4 of a
turn. The display on the drive will show the
actual motor amps.
Operation checkpoints:
•
Motor rotates smoothly
•
Motor rotates in correct direction. (If motor
does not rotate in the proper direction,
stop the motor and remove power from the
Drive. Switch motor connections T1 (U)
and T2 (V) at the Drive to change
direction).
•
Motor has no abnormal vibration or noise.
•
Acceleration and deceleration are smooth.
•
Unit is not overloaded. (Displayed current
does not exceed drive rated current).
Press the
key.
STOP
RESET
RUN
This completes the startup.
Make further programming
changes as required.
(1)
The number in the display may be different than shown.
Prepare to test run the
drive from the Digital
Operator. Motor should be
disconnected from the load.
This will set the drive into the
“Local” mode, and bring up
the motor current display.
Press
several times until the “LO/RE”
LED is lit.
DSPL
LO/RE
LO/RE
IOUT
Display the drive’s output current by pressing
four times. Turn the Digital Operator
Pot all the way to the left (counter-clockwise).
DSPL
Press the
key once.
V
IOUT
(1)
Summary of Contents for GPD315/V7-4X
Page 1: ...GPD 315 V7 and V7 4X Technical Manual...
Page 4: ......
Page 20: ...xvi...
Page 22: ......
Page 40: ...1 18...
Page 52: ...3 2...
Page 56: ...4 4...
Page 101: ...5 45 PID Block Diagram...
Page 130: ...A1 8...
Page 134: ...A3 2...
Page 136: ...A4 2...
Page 146: ...A6 6...
Page 150: ...A7 4...
Page 154: ...A8 4...
Page 158: ......
Page 160: ......