5-36
D.
n115 : Stall Prevention Above Base Speed During Running
Factory setting: 0
Range: 0 or 1
Setting
Function
0
Disabled (level is based on setting of n094)
1
Enabled (level at Fmax, n011, is n094 x 0.4)
E.
n116 : Stall Prevention During Run, Accel/Decel Time Select
Factory setting: 0
Range: 0 or 1
Setting
Function
0
Follows accel/decel #1 (n019, n020) or accel/decel #2
(n021,n022)
Note: Multi-Function input selectable
1
Follows accel/decel #2 (n021,n022) always
5.23 STALL PREVENTION