6-6
Fault Display
Digital
RUN (Green)
Drive
Explanation
Causes and
Operator
ALARM (Red)
Status
Corrective Actions
EF
Check the external circuit
(External fault)
(sequence).
Drive receives an
external fault input from
control circuit terminal.
EF0: External fault
reference through
MODBUS
communications
EF1: External fault
input command from
control circuit
terminal S1
EF2: External fault input
command from control
circuit terminal S2
EF3: External fault input
command from control
circuit terminal S3
EF4: External fault input
Protective
command from control
Operation.
circuit terminal S4
Output is
EF5: External fault input
shut OFF
command from control
and motor
circuit terminal S5
coasts to
EF6: External fault input
a stop.
command from control
circuit terminal S6
EF7: External fault input
command from control
circuit terminal S7
CPF-00
Cycle power after checking
Drive cannot
the digital operator is
communicate with the digital
securely mounted.
operator for 5 sec. or
If the fault remains,
more when power is
replace the digital operator
turned ON.
or drive.
CPF-01
Cycle power after checking
Transmission fault
the digital operator is
occurred for 5 sec or more
securely mounted.
when transmission starts
If the fault remains,
with the digital operator.
replace the digital operator
or drive.
CPF-04
• Record all parameter
EEPROM fault of drive
data and initialize the
control circuit is detected.
constants. (Refer to
paragraph 5.__ for
constant initialization.)
• Cycle power.
If the fault remains,
replace the drive.
Table 6-2. Fault Displays and Corrective Actions - Continued
Summary of Contents for GPD315/V7-4X
Page 1: ...GPD 315 V7 and V7 4X Technical Manual...
Page 4: ......
Page 20: ...xvi...
Page 22: ......
Page 40: ...1 18...
Page 52: ...3 2...
Page 56: ...4 4...
Page 101: ...5 45 PID Block Diagram...
Page 130: ...A1 8...
Page 134: ...A3 2...
Page 136: ...A4 2...
Page 146: ...A6 6...
Page 150: ...A7 4...
Page 154: ...A8 4...
Page 158: ......
Page 160: ......