Fault Codes
Parameter Setting Error
- Inverter can’t run. The fault is displayed
on the digital operator, and the fault relay is not activated.
Inverter kVA setting error.
OPE01
kVA Selection
ope 1
OPE02
Limit
Constant data is out of range. 506 digital operator will
display OPE06.
ope 6
Possible Cause(s):
The control board was replaced and the kVA parameter is set incorrectly.
Corrective Action:
Enter the correct kVA setting (O2-4 for GPD515/G5) and (n115 for
GPD506/P5) by referring to the inverter model number.
Possible Cause(s):
Parameter set above the allowable range.
Corrective Action:
Verify the program settings.