11 General Class Objects
YASKAWA ELECTRIC
SIEP C730600 43A YASKAWA AC Drive-Option Card DeviceNet Technical Manual
65
DeviceNet Fault Code Conversion Table
1
11
Warning
Warning
0: No Warning
1: Warning
{
–
Byte
–
0
1
12
Fault Reset
Fault Reset
0: No Fault Reset
1: Fault Reset
{
{
Byte
0,1
0
1
13
Fault Code
Current Fault Refer to
Fault Code Conversion Table on
page 65
{
–
Word
–
0000
1
15
Control from Net (Status)
Run Command from DeviceNet
0: Enables the run command from
except for DeviceNet
1: Enables the run command from
DeviceNet
{
–
Byte
–
0
1
16
DeviceNet Fault Mode
Normal 2 (vendor specific)
{
–
Byte
–
2
1
17
Force Fault
External fault
0: No External Fault
1: External fault (EF0)
Triggered by the rising edge of the
signal
{
{
Byte
0,1
0
1
18
Force Reset
External fault status
0: No External Fault
1: External fault
Triggered by the rising edge of the
signal.
{
–
Byte
–
0
Drive Fault Code [Dec]
(MEMOBUS/Modbus #0080hex)
DeviceNet Fault Code [hex]
Description
0
0000
None
2
3220
DC Bus Undervolt (Uv1)
3
5110
CTL PS Undervolt (Uv2)
4
3222
MC Answerback (Uv3)
6
2120
Ground Fault (GF)
7
2300
Over Current (oC)
8
3210
DC Bus Overvolt (ov)
9
4200
Heatsink Overtemp (oH)
10
4210
Heatsink Max Temp (oH1)
11
2220
Motor Overload (oL1)
12
2200
Inv Overload (oL2)
13
2221
Overtorque Det 1 (oL3)
14
2222
Overtorque Det 2 (oL4)
15
7110
DynBrk Transistor (rr)
16
7112
DynBrk Resistor (rH)
17
9000
External Fault 3 (EF3)
18
9000
External Fault 4 (EF4)
19
9000
External Fault 5 (EF5)
20
9000
External Fault 6 (EF6)
21
9000
External Fault 7 (EF7)
22
9000
External Fault 8 (EF8)
24
7310
Overspeed Det (oS)
25
7310
Speed Deviation (dEv)
26
7301
PG Open (PGo)
27
3130
Input Phase Loss (PF)
28
3130
Output Phase Loss (LF)
29
5210
Motor Overheat 1 (PTC input) (oH3)
30
5300
Operator Disconnected (oPr)
Instance
ID
Attribute
Name
Description
Get Set
Size
Range
Default