10 Input Assemblies (Drive Produces)
YASKAWA ELECTRIC
SIEP C730600 43A YASKAWA AC Drive-Option Card DeviceNet Technical Manual
49
Parameter
Data
Running
Running
0: Stop
1: Forward or Reverse Running
ZSP
Zero Speed
0: Running
1: Stop or DC Injection Braking
REV Running
Reverse Running
0: Not Reverse Running
1: Reverse Running
Reset
Reset
0: No Reset
1: Reset
Speed Agree
Speed Agree
0: No Speed Agree
1: Actual speed at speed reference
READY
Drive Ready
0: Not Ready
1: Ready
ALARM
Drive Alarm
0: No Drive Alarm
1: Alarm
FAULT
Drive Fault
0: No Drive Fault
1: Fault
OPE
OPE Fault
0: No OPExx Fault
1: OPExx
UV
Under Voltage
0: No Under Voltage
1: Under Voltage
Local/Remote
Status of Run command from Network
0: Run command is not from network
1: Run command is from network
Multi-Function Digital Output
Terminal M1/M2
0: Terminal M1/M2 OFF
1: Terminal M1/M2 ON
Multi-Function Photo Coupler 1
Terminal P1
0: Terminal P1 OFF
1: Terminal P1 ON
Multi-Function Photo Coupler 2
Terminal P2
0: Terminal P2 OFF
1: Terminal P2 ON
Output Frequency
Actual Drive Speed
Monitors drive output frequency
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.
Frequency Reference
Frequency Reference
Monitors drive frequency reference
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.
Actual Current
Actual Output Current
Monitors drive output current
Unit is 0.01 A for drives set up to 11 kW in Heavy Duty or Normal Duty and 0.1 A for drives set up for 15
kW and above.
Unit is not affected by Current Scale CS.