23
YASKAWA AC Drive
CR700
Catalog
|
KAEP C
710617
24
|
YASKAWA
Note:
1. Perform Rotational Auto-Tuning to achieve specifi cations listed for Open Loop Vector Control, Close Loop Vector Control and Advanced Open Loop
Vector Control.
2. Install the drive in an environment matching the specifi cations in the table above for optimum performance life.
*
Altitudes over
1000 m and up to 3000 m are possible by derating the output current by 1% for every 100 m.
Contact Yaskawa or your nearest sales representative for details.
Item
Specifi cations
Envir
onment
Area of Use
Indoors
・
chemical gas: IEC
60721-3-3: 3 C2
・
solid particle: IEC
60721-3-3: 3 S2
Power Supply
Overcurrent Category
III
Ambient Temperature
Open chassis type (IP
20): -10˚C to +50˚C
Enclosed wall-mounted type (UL Type
1):
−
10˚C to
+
40˚C
・
Do not use the drive in a location where the temperature changes suddenly to improve the drive reliability.
・
When installing the drive in an enclosure, use a cooling fan or air conditioner to keep the internal air temperature in
the permitted range.
・
Do not let the drive freeze.
・
Derate the output current and output voltage to install the drive in areas with ambient temperatures
≤
60 ˚C.
Humidity
95% RH or less (no condensation)
Storage Temperature
Short-term temperature during transportation is -
20 ˚C to
+
70 ˚C
Surrounding Area
Pollution degree
2 or less
Install the drive in an area without:
・
Oil mist, corrosive or fl ammable gas, or dust
・
Metal powder, oil, water, or other unwanted materials
・
Radioactive materials or fl ammable materials, including wood
・
Harmful gas or fl uids
・
Salt
・
Direct sunlight
Keep wood or other fl ammable materials away from the drive.
Altitude
1000 m or less
*
Shock
・
10 Hz to 20 Hz, 1 G (9.8 m/s
2
)
・
20 Hz to 55 Hz, Catalog code CR70
2003 to 2180, 4002 to 4150: 0.6 G (5.9 m/s
2
),
Catalog code CR
70
2215 to 2415, 4180 to 4605: 0.2 G (2.0 m/s
2
)
Standards Compliance
・
UL
61800-5-1
・
EN
61800-3:2004+A1:2012
・
IEC/EN
61800-5-1
・
Two Safe Disable inputs and
1EDM output according to ISO/EN13849-1 Cat.3 Ple
,
IEC/EN
61508 SIL3
Note: Used by setting functions to multi-function digital output terminals.
Protection Design
Open chassis type (IP
20), Enclosure wall-mounted type (UL Type 1)
Note: Installing the UL Type
1 kit to a drive in an open chassis type (IP20) makes the drive compliant with an
enclosure wall-mounted type (UL Type
1).
Featur
es
Catalog Code /
Selecting the Capacity
Basic
Instructions
Standar
d
Specifi
cations
Standar
d
Connection Diagram
Terminal
Specifi
cations
Dimensions
Fully
-Enclosed
Design
Peripheral Devices
and Options
Application
Notes
Gl
o
b
a
l S
e
rv
ic
e
Ne
tw
o
rk
Standar
d
Specifi
cations