38
YASKAWA
|
YASKAWA AC Drive
CR700
Catalog
|
KAEP C710617 24
Device selection is based on the motor capacity.
Make sure that the rated breaking capacity is higher than the
shortcircuit current for the power supply.
Protect the wiring to withstand the short
-
circuit current for the
power supply using a combination of fuses if the rated breaking
capacity of the circuit breaker or ground fault interrupter is
insuffi cient, such as when the power transformer capacity is large.
Ground Fault Interrupter, Circuit Breaker
200 V Class
400 V Class
Ground Fault Interrupter
【
Mitsubishi Electric Corporation
】
*
1: The AC or DC reactor is connected to the drive.
*
2: Icu: Rated ultimate short-circuit breaking capacity
Ics: Rated service short-circuit breaking capacity
*
1: The AC or DC reactor is connected to the drive.
*
2: Icu: Rated ultimate short-circuit breaking capacity
Ics: Rated service short-circuit breaking capacity
Circuit Breaker
【
Mitsubishi Electric Corporation
】
Motor
Capacity
(kW)
Ground Fault Interrupter
Circuit Breaker
Without Reactor
*
1
With Reactor
*
1
Without Reactor
*
1
With Reactor
*
1
Model
Rated
Current
(A)
Interrupt
Capacity (kA)
Icu/Ics
*
2
Model
Rated
Current
(A)
Interrupt
Capacity (kA)
Icu/Ics
*
2
Model
Rated
Current
(A)
Interrupt
Capacity (kA)
Icu/Ics
*
2
Model
Rated
Current
(A)
Interrupt
Capacity (kA)
Icu/Ics
*
2
0.4
NV
32-SV
5
10/10
NV
32-SV
5
10/10
NF
32-SV
5
7.5/7.5
NF
32-SV
5
7.5/7.5
0.75
NV
32-SV
10
10/10
NV
32-SV
10
10/10
NF
32-SV
10
7.5/7.5
NF
32-SV
10
7.5/7.5
1.5
NV
32-SV
15
10/10
NV
32-SV
10
10/10
NF
32-SV
15
7.5/7.5
NF
32-SV
10
7.5/7.5
2.2
NV
32-SV
20
10/10
NV
32-SV
15
10/10
NF
32-SV
20
7.5/7.5
NF
32-SV
15
7.5/7.5
3
NV
32-SV
30
10/10
NV
32-SV
20
10/10
NF
32-SV
30
7.5/7.5
NF
32-SV
20
7.5/7.5
3.7
5.5
NV
63-SV
50
15/15
NV
63-SV
40
15/15
NF
63-SV
50
15/15
NF
63-SV
40
15/15
7.5
NV
125-SV
60
50/50
NV
63-SV
50
15/15
NF
125-SV
60
50/50
NF
63-SV
50
15/15
11
NV
125-SV
75
50/50
NV
125-SV
75
50/50
NF
125-SV
75
50/50
NF
125-SV
75
50/50
15
NV
250-SV
125
85/85
NV
125-SV
100
50/50
NF
250-SV
125
85/85
NF
125-SV
100
50/50
18.5
NV
250-SV
150
85/85
NV
250-SV
125
85/85
NF
250-SV
150
85/85
NF
250-SV
125
85/85
22
−
−
−
NV
250-SV
150
85/85
−
−
−
NF
250-SV
150
85/85
30
−
−
−
NV
250-SV
175
85/85
−
−
−
NF
250-SV
175
85/85
37
−
−
−
NV
250-SV
225
85/85
−
−
−
NF
250-SV
225
85/85
45
−
−
−
NV
400-SW
250
85/85
−
−
−
NF
400-CW
250
50/25
55
−
−
−
NV
400-SW
300
85/85
−
−
−
NF
400-CW
300
50/25
75
−
−
−
NV
400-SW
400
85/85
−
−
−
NF
400-CW
400
50/25
90
−
−
−
NV
630-SW
500
85/85
−
−
−
NF
630-CW
500
50/25
110
−
−
−
NV
630-SW
600
85/85
−
−
−
NF
630-CW
600
50/25
Motor
Capacity
(kW)
Ground Fault Interrupter
Circuit Breaker
Without Reactor
*
1
With Reactor
*
1
Without Reactor
*
1
With Reactor
*
1
Model
Rated
Current
(A)
Interrupt
Capacity (kA)
Icu/Ics
*
2
Model
Rated
Current
(A)
Interrupt
Capacity (kA)
Icu/Ics
*
2
Model
Rated
Current
(A)
Interrupt
Capacity (kA)
Icu/Ics
*
2
Model
Rated
Current
(A)
Interrupt
Capacity (kA)
Icu/Ics
*
2
0.4
NV
32-SV
5
5/5
NV
32-SV
5
5/5
NF
32-SV
3
2.5/2.5
NF
32-SV
3
2.5/2.5
0.75
NV
32-SV
5
5/5
NV
32-SV
5
5/5
NF
32-SV
5
2.5/2.5
NF
32-SV
5
2.5/2.5
1.5
NV
32-SV
10
5/5
NV
32-SV
10
5/5
NF
32-SV
10
2.5/2.5
NF
32-SV
10
2.5/2.5
2.2
NV
32-SV
15
5/5
NV
32-SV
10
5/5
NF
32-SV
15
2.5/2.5
NF
32-SV
10
2.5/2.5
3
NV
32-SV
20
5/5
NV
32-SV
15
5/5
NF
32-SV
20
2.5/2.5
NF
32-SV
15
2.5/2.5
3.7
5.5
NV
32-SV
30
5/5
NV
32-SV
20
5/5
NF
32-SV
30
2.5/2.5
NF
32-SV
20
2.5/2.5
7.5
NV
32-SV
30
5/5
NV
32-SV
30
5/5
NF
32-SV
30
2.5/2.5
NF
32-SV
30
2.5/2.5
11
NV
63-SV
50
7.5/7.5
NV
63-SV
40
7.5/7.5
NF
63-SV
50
7.5/7.5
NF
63-SV
40
7.5/7.5
15
NV
125-SV
60
25/25
NV
63-SV
50
7.5/7.5
NF
125-SV
60
25/25
NF
63-SV
50
7.5/7.5
18.5
NV
125-SV
75
25/25
NV
125-SV
60
25/25
NF
125-SV
75
25/25
NF
125-SV
60
25/25
22
−
−
−
NV
125-SV
75
25/25
−
−
−
NF
125-SV
75
25/25
30
−
−
−
NV
125-SV
100
25/25
−
−
−
NF
125-SV
100
25/25
37
−
−
−
NV
250-SV
125
36/36
−
−
−
NF
250-SV
125
36/36
45
−
−
−
NV
250-SV
150
36/36
−
−
−
NF
250-SV
150
36/36
55
−
−
−
NV
250-SV
175
36/36
−
−
−
NF
250-SV
175
36/36
75
−
−
−
NV
250-SV
225
36/36
−
−
−
NF
250-SV
225
36/36
90
−
−
−
NV
400-SW
250
42/42
−
−
−
NF
400-CW
250
25/13
110
−
−
−
NV
400-SW
300
42/42
−
−
−
NF
400-CW
300
25/13
132
−
−
−
NV
400-SW
350
42/42
−
−
−
NF
400-CW
350
25/13
160
−
−
−
NV
400-SW
400
42/42
−
−
−
NF
400-CW
400
25/13
200
−
−
−
NV
630-SW
500
42/42
−
−
−
NF
600-CW
630
36/18
220
−
−
−
NV
630-SW
630
42/42
−
−
−
NF
600-CW
630
36/18
250
−
−
−
NV
630-SW
630
42/42
−
−
−
NF
600-CW
630
36/18
315
−
−
−
NV
800-SEW
800
42/42
−
−
−
NF
800-CEW
800
36/18
Note:
200 V models 22 kW and above come with a built-in DC reactor that
improves the power factor.
Note:
400 V models 22 kW and above come with a built-in DC reactor that
improves the power factor.
Peripheral Devices and Options