34
YASKAWA
|
YASKAWA AC Drive
CR700
Catalog
|
KAEP C
710617
24
・
Cooling Design for
Fully-Enclosed Panel
・
Ventilation Space
Drive Watts Loss Data
The Open Chassis type drive can be installed in a fully-enclosed panel.
For installing the drive with capacity of
200 V class
22 kW or 400 V class 22 kW, be sure to leave
enough clearance during installation for
suspension brackets on both side of the unit and
main circuit wiring for maintenance.
Intake air temperature for external heatsink
Heatsink side:
50 ˚C
Open chassis side:
50 ˚C
Use only an open chassis type for the
external heatsink.
An open chassis model in a protective enclosure with the heatsink inside the panel allows for intake air temperature up to
50
˚C.
The heatsink can alternatively be mounted outside the control panel, thus reducing the amount of heat inside the panel and
allowing for a more compact set up.
・
Mounting the External Heatsink
Catalog Code CR
70A2
003
005
008
011
014
018
025
033
047
060
075
088
115
145
Rated Output Current
A
3.2
5
8
11
14
17.5
25
33
47
60
75
88
115
145
Carrier Frequency
kHz
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Heat Loss
*
W
Internal
5
9
16
21
27
32
36
53
59
110
134
147
209
265
Heatsink
7
13
27
42
59
74
95
126
155
299
357
467
613
748
Total Heat Loss
12
22
43
63
86
106
131
179
214
409
491
614
822
1013
Catalog Code CR
70A2
180
215
283
346
415
Rated Output Current
A
180
215
283
346
415
Carrier Frequency
kHz
2
2
2
2
2
Heat Loss
*
W
Internal
297
362
459
520
603
Heatsink
935
1144
1508
1769
2216
Total Heat Loss
1232
1506
1967
2289
2819
200 V Class
Catalog Code CR
70A4
091
112
150
180
216
260
304
371
414
453
605
Rated Output Current
A
91
112
150
180
216
260
304
371
414
453
605
Carrier Frequency
kHz
2
2
2
2
2
2
2
2
2
2
2
Heat Loss
*
W
Internal
225
275
385
397
564
573
728
976
1118
1272
1495
Heatsink
658
804
1012
1279
1484
1709
2075
2778
3133
3559
4500
Total Heat Loss
883
1079
1397
1676
2048
2282
2803
3754
4251
4831
5995
Catalog Code CR
70A4
002
003
005
006
007
009
015
018
024
031
039
045
060
075
Rated Output Current
A
1.8
3.4
4.8
5.5
7.2
9.2
14.8
18
24
31
39
45
60
75
Carrier Frequency
kHz
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Heat Loss
*
W
Internal
13
12
21
28
35
44
55
63
93
121
132
141
188
188
Heatsink
14
18
32
50
70
86
116
141
206
286
331
365
497
557
Total Heat Loss
27
30
53
78
105
130
171
204
299
407
463
506
685
745
400 V Class
*
Heat loss is calculated in the following conditions:
・
200 V class: Input voltage 220 V, power frequency 60 Hz, load ratio 100%
・
400 V class: Input voltage 440 V, power frequency 60 Hz, load ratio 100%
Contact your Yaskawa or nearest agent when not calculating heat loss in the above conditions.
Heatsink
Attachment for
external heatsink
(Option)
120 mm min.
Airflow
Airflow
120 mm min.
50 mm min.
Side Clearance
Top/Bottom Clearance
50 mm min.
30 mm min.
Fully-enclosed panel
60˚C
50˚C
Air temperature
at top of panel
−
10 to
+
60˚C
IP
20/Open Chassis
Drive intake temperature
−
10 to
+
50˚C
Ambient temperature
50˚C
Bottom cover
Heatsink
Fully-Enclosed Design