2.3 Device Description File
2.2.3 Operating Environment Specifications
2-7
2
264IF-01 Module
2.2.3 Operating Environment Specifications
2.3 Device Description File
The device description file is a profile that states the information of a device, and it is provided by the slave device
manufacturer. An EtherCAT network can be configured by installing this file in the configuration tool of the master
device. The device description file is written in the XML format. (It is a setting file equivalent to the EDS file used with
DeviceNet, Ethernet/IP.)
Obtain the device description file by either of the following methods.
• The MPE720 installation disk
• Downloading from the Yaskawa website (the e-mechatronics site: http://www.e-mechatronics.com/index.jsp)
Table 2.3 Operating Environment Specifications for the 264IF-01 Module
Item Specifications
Environmental
Conditions
Ambient Operating
Temperature
0 to +55
°
C
Ambient Storage
Temperature
−
25 to +85
°
C
Ambient Operating
Humidity
30% to 95% RH (with no condensation)
Ambient Storage Humidity
5% to 95% RH (with no condensation)
Pollution Level
Pollution level 2 (conforming to JIS B 3502)
Operating Altitude
2,000 m above sea level or lower
Mechanical
Operating
Conditions
Vibration Resistance
Vibration amplitude/acceleration
16.7 Hz
14.7 m/s
2
10
≤
f < 57 Hz
0.075 mm of single-amplitude
57
≤
f
≤
150 Hz
9.8 m/s
2
of fixed acceleration
Shock Resistance
Peak acceleration of 147 m/s
2
twice for 11 ms each in the X, Y, and Z direc-
tions
Electrical
Operating
Conditions
Noise Resistance
Conforming to EN 61000-6-2, EN 61000-6-4, EN 55011 (Group 1 Class A)
Installation
Requirements
Ground Ground
to
100
Ω
max.
Cooling Method
Natural cooling