7800 SERIES EC7890A,B/RM7890A,B RELAY MODULE

65-0204–1

4

Table 2. Flame Detection Systems.

a

A 0.8 sec Flame Failure Response Time Amplifier is required when the Relight option is (JR2 is intact, see Table 3). The RM7890
will lock out and indicates a Fault 46 when a 3.0 second FFRT is used and jumper JR2 (Lockout) is not clipped and removed.

b

Order flame rod separately; see holder Instructions.

c

The C7012A,C, C7027, C7035 and C7044 Flame Detectors should be used only on burners that cycle on-off at least once
every twenty-four hours. Appliances with burners that remain on continuously for twenty-four hours or longer should use the
C7012E,F Flame Detector with the R7847C Amplifier or the C7076A,D Flame Detector with the R7886A Amplifier or the C7061
Flame Detector with the R7861 Amplifier as the ultraviolet flame detection system.

d

Use with EC7890B or RM7890B only.

e

Circuitry tests the flame signal amplifier at least 12 times a minute during burner operation and shuts down the burner if the
amplifier fails.

f

Use 

only Honeywell Photocell, part no. 38316.

g

Circuitry tests all electronic components in the flame detection system (amplifier and detector) 12 times a minute during burner
operation and shuts down the burner if the detection system fails.

h

When an R7861A is used with an EC7890B, the application requires the use of a step-down transformer. See Fig. 14.

Plug-in Flame Signal Amplifiers

Applicable Flame Detectors

Type

Color

Self-Checking

Model

Flame
Failure
Response
Time

a

Fuel

Type

Models

Rectification

Green

No

R7847A

.8 or 3 sec

Gas

Rectifying Flame  
Rod Holders

b

C7004, C7007, C7011.
Complete Assemblies:
C7008, C7009, Q179.

No

R7847A

.8 or 3 sec

Oil

Rectifying  
Photocell

C7003, C7010, C7013,
C7014.

No

R7847A

3 sec

Gas, oil,
coal

Ultraviolet
(PurplePeeper)

C7012A,C.

c,d

Dynamic  
Ampli-Check®

R7847B

e

.8 or 3 sec

Gas

Rectifying Flame  
Rod Holders

b

C7004, C7007, C7011.
Complete Assemblies:
C7008, C7009, Q179.

Dynamic  
Ampli-Check®

R7847B

e

.8 or 3 sec

Oil

Rectifying  
Photocell

f

C7003, C7010, C7013,
C7014.

Dynamic  
Ampli-Check®

R7847B

e

3 sec

Gas, oil,
coal

Ultraviolet  
(Purple Peeper)

C7012A,C.

c

Dynamic  
Self-Check

d

R7847C

g

3 sec

Gas, oil,
coal

Ultraviolet  
(Purple Peeper)

C7012E,F.

Infrared

Red

No

R7848A

3 sec

Gas, oil,
coal

Infrared  
(Lead Sulfide)

C7015.

Dynamic  
Ampli-Check®

R7848B

e

3 sec

Gas, oil
coal

Infrared  
(Lead Sulfide)

C7015.

Ultraviolet

Purple

No

R7849A

.8 or 3 sec

Gas, oil

Ultraviolet
(Minipeeper)

C7027, C7035, C7044.

c

Dynamic  
Ampli-Check®

R7849B

e

.8 or 3 sec

Gas, oil

Ultraviolet
(Minipeeper)

C7027, C7035, C7044.

c

Dynamic  
Self-Check

d,h

R7861A

3 sec

Gas, oil,
coal

Ultraviolet

C7061.

Blue

Dynamic  
Self-Check

d

R7886A

g

3 sec

Gas, oil,
coal

Ultraviolet
(Adjustable
Sensitivity)

C7076.

Summary of Contents for 7800 Series

Page 1: ...umpers GENERAL The Yamatake Honeywell EC7890A B RM7890A B is a micro processor based integrated burner control for automatically fired gas oil or combination fuel single burner applications Except whe...

Page 2: ...onnection between the subbase and the control panel or the equipment The earth ground wire must be capable of conducting the current to blow the 20A fuse or breaker in event of an internal short circu...

Page 3: ...urface corrosion 2 Range of allowable operating frequencies is 45 to 66 Hz 3 2000 VA maximum connected load to 7890 Assembly Environmental Ratings Ambient Temperature Operating 40 F to 140 F Storage 6...

Page 4: ...er if the detection system fails h When an R7861A is used with an EC7890B the application requires the use of a step down transformer See Fig 14 Plug in Flame Signal Amplifiers Applicable Flame Detect...

Page 5: ...NAGER part no ZM7850A1001 Network Interface Unit part no Q7700B1004 Communication Interface ControlBus Module part no QS7800A1001 ControlBus 5 Wire Electrical Connector part no 203541 DATA CONTROLBUS...

Page 6: ...2 155 BURNER CONTROL THREADED MOUNTING HOLES 2 10 32 UNF 1 25 FLAME ROD TARGET CERAMIC INSULATORS IGNITION ELECTRODE Q179C ONLY BRACKET M1983 3 1 8 79 1 21 32 42 1 13 32 36 3 8 10 1 2 13 1 1 16 27 25...

Page 7: ...11 BSP P1 INTERNAL THREADS DIN APPROVED C7035A1064 HAS 1 2 14 BSP F INTERNAL THREADS MODEL AVAILABLE WITH 12 FOOT 3 66 METER LEADWIRES 2 3 INSERTION DEPTH 6 FOOT 1 83 METER LEADWIRES 2 3 M1945A 2 5 8...

Page 8: ...nal system fault occurred c Main valve terminal is not energized d No flame present and configuration jumper is selected for lockout e Pilot valve terminal is not energized SAFETY PROVISIONS Internal...

Page 9: ...tinually through STANDBY to detect any possibility of a runaway detector or a flame If a flame exists a safety shutdown occurs A standard amplifier is energized continually through STANDBY if a flame...

Page 10: ...f part 15 of FCC rules which are designed to provide reasonable protection against such interference when operated in a commercial environment Operation of this equipment in a residential area is like...

Page 11: ...must be capable of conducting the current to blow the 20A fuse or breaker in event of an internal short circuit The 7890 needs a low impedance ground connection to the equipment frame which in turn n...

Page 12: ...AY TO SWITCH THE F LEAD THE RELAY MUST HAVE GOLD CLAD OR GOLD FLASH CONTACTS AND A 120 VAC COIL POWER THE RELAY COIL FROM THE Q7800 SUBBASE TERMINAL 8 CONNECT THE RELAY CONTACTS BETWEEN THE F LEAD OF...

Page 13: ...ION TRANSFORMER MAIN VALVE 1 Q7800 2 2 3 3 5 4 L2 FOR A CONTINUOUS OR STANDING PILOT INSTALL AN EXTERNAL RELAY TO SWITCH THE F LEAD THE RELAY MUST HAVE GOLD CLAD OR GOLD FLASH CONTACTS AND A 230 VAC C...

Page 14: ...for electrical signal voltage probes 3 Make sure no subbase wiring is projecting beyond the terminal blocks Tuck in wiring against the back of the subbase so it does not interfere with the knife blad...

Page 15: ...required checkout tests Installing The Flame Detector NOTE Table 2 and Fig 13 list the flame detection systems available for use with the 7890 Make sure the correct combination of amplifier and flame...

Page 16: ...b 2a EARTH GROUND C7076A OR C7076D TERMINAL BLOCK L2 COMMON L1 HOT G F X X FLAME ROD G F X X PHOTOCELL 1 FLAME DETECTOR LEADS ARE COLOR CODED THE BLUE LEAD MUST BE CONNECTED TO THE F TERMINAL AND THE...

Page 17: ...Up Safe Start Check The 7890 verifies that a flame does not exist and proceeds into the Ignition Trial If a flame is present the 7890 will recycle to the STANDBY period If the critical loads are not i...

Page 18: ...a jumper on the subbase 3 Before continuing to the next test be sure to remove the test jumper s used in the previous tests 4 Replace all limits and interlocks not operating properly Do not bypass lim...

Page 19: ...mper s WARNING Make sure all manual fuel shutoff valves are closed MPORTANT Low fuel pressure limits if used can be open Bypass them with jumpers for the remaining Static tests if required Table 4 Sta...

Page 20: ...mum sensitivity 0 300 Vac capability 0 6000 ohm capability 0 10 Vdc capability Checkout Summary Preliminary inspection all installations Flame signal measurement all installations Initial lightoff che...

Page 21: ...the peaks and valleys caused by the self checking operation 6 The meter reading must be as specified in Table 5 after all tests are completed and all adjustments are made As an option the flame signal...

Page 22: ...on the subbase and close the master switch and return to step 4 7 When the pilot ignites measure the flame signal If the pilot flame signal is unsteady or approaching the 1 25 Vdc minimum value adjus...

Page 23: ...for flame stability and input rating If a second stage is used proceed to step 18 P Shut down the system by opening the burner switch or by lowering the setpoint of the operating controller Make sure...

Page 24: ...itches L Run the system through another cycle to check for normal operation M Return the system to normal operation Ignition Interference Test All Flame Rods Test to be sure that a false signal from a...

Page 25: ...or Ignition Spark Response Test All Ultraviolet Detectors Test to be sure that the ignition spark is not actuating the FLAME LED 1 Close the pilot and main burner manual fuel shutoff valve s 2 Start t...

Page 26: ...uence status messages indicating INITIATE STANDBY SAFE START CHECK PILOT IGN and RUN The selectable messages also provide visual indication current status and historical status of the equipment such a...

Page 27: ...line voltage is at a sufficient level for proper operating parameters STANDBY The LED indicates the burner status POWER The burner can be placed in STANDBY by opening the burner switch or if the opera...