background image

7800 SERIES EC7890A,B/RM7890A,B RELAY MODULE

65-0204–1

11

Mounting Wiring Subbase

NOTE:

For installation dimensions, see Fig. 1 or 2.

1

Mount the subbase in any position except horizontally
with the bifurcated contacts pointing down. The standard
vertical position is recommended. Any other position
decreases the maximum ambient temperature rating.

2

Select a location on a wall, burner or electrical panel.
The Q7800 can be mounted directly in the control
cabinet. Be sure to allow adequate clearance for
servicing, installation, access and removal of the 7890,
dust cover, flame amplifier, flame amplifier signal
voltage probes, electrical signal voltage probes and
electrical field connections.

3

For surface mounting, use the back of the subbase as
a template to mark the four screw locations. Drill the
pilot holes.

4

Securely mount the subbase using four no. 6 screws.

WIRING

1

a. For proper subbase wiring, refer to Fig. 7.
b.

For proper remote wiring of the Keyboard Display
Module; refer to the Specifications for the
Keyboard Display Module (65-0090),
Communication Interface Base Unit (63-2278),
DATA CONTROLBUS MODULE™ (65-0091) or
Extension Cable Assembly (65-0131).

2

Disconnect the power supply from the main disconnect
before beginning installation to prevent electrical shock
and equipment damage. More than one disconnect
may be involved.

3

All wiring must comply with all appropriate electrical
codes, ordinances and regulations. Wiring, where
required, must comply with NEC Class 1 (Line
Voltage) wiring.

4

Recommended wire size and type: Use no. 14, 16, or 18
copper conductor (TTW60C or THW75C or THHN90C)
600 volt insulation wire for all line voltage terminals. For
high temperature installations, use wire selected for a
temperature rating above the maximum operating
temperature. All leadwires must be moisture resistant.

5

Recommended grounding practices:

a.

Use the earth ground to provide a connection
between the subbase and the control panel or the
equipment. The earth ground wire must be
capable of conducting the current to blow the 20A

fuse (or breaker) in event of an internal short
circuit. The 7890 needs a low impedance ground
connection to the equipment frame which, in turn,
needs a low impedance connection to earth
ground. For a ground path to be low impedance
at RF frequencies, the connection must be made
with minimum length conductors that have a
maximum surface area. Wide straps or brackets
are preferred rather than leadwires. Be careful to
verify that mechanically tightened joints along the
ground path, such as pipe or conduit threads or
surfaces held together with fasteners, are free of
nonconductive coatings and are protected
against mating surface corrosion.

b.

The earth ground terminal for each 7890 must be
grounded to the metal control panel with wire as
short as practical. Each ground wire must be
capable of carrying a fault current equal to the
rating of the protective fuse (20A). A number 14
copper conductor is adequate but wide straps or
brackets are preferred rather than leadwires.

6

Recommended wire routing for flame detector
leadwires:

Do not run high voltage ignition transformer
wires in the same conduit with the flame
detection wiring.

Do not route scanner wires in a conduit with line
voltage circuits.

Enclose scanner wires without armor cable in
metal cable or conduit.

Follow directions given in the flame detector
Instructions.

7

Maximum wire lengths:

a.

For the 7890, the maximum length of leadwire to
the control terminal input is 300 feet.

b.

For the flame detector leadwires, the maximum
flame sensor leadwire length is limited by the
flame signal strength.

8

Make sure loads do not exceed the terminal ratings.
Refer to the label on the 7890 or to the ratings in the
Specifications, see Table 1A or 1B.

9

Check the power supply circuit. The voltage and
frequency tolerance must match those of the 7890. A
separate power supply circuit may be required for the
7890 with the required disconnect means and overload
protection added.

J

Check all wiring circuits and complete the Static
Checkout, see Table 4, before installing the 7890 on the
subbase.

K

Install all electrical connectors.

L

Restore power to the panel.

Summary of Contents for 7800 Series

Page 1: ...umpers GENERAL The Yamatake Honeywell EC7890A B RM7890A B is a micro processor based integrated burner control for automatically fired gas oil or combination fuel single burner applications Except whe...

Page 2: ...onnection between the subbase and the control panel or the equipment The earth ground wire must be capable of conducting the current to blow the 20A fuse or breaker in event of an internal short circu...

Page 3: ...urface corrosion 2 Range of allowable operating frequencies is 45 to 66 Hz 3 2000 VA maximum connected load to 7890 Assembly Environmental Ratings Ambient Temperature Operating 40 F to 140 F Storage 6...

Page 4: ...er if the detection system fails h When an R7861A is used with an EC7890B the application requires the use of a step down transformer See Fig 14 Plug in Flame Signal Amplifiers Applicable Flame Detect...

Page 5: ...NAGER part no ZM7850A1001 Network Interface Unit part no Q7700B1004 Communication Interface ControlBus Module part no QS7800A1001 ControlBus 5 Wire Electrical Connector part no 203541 DATA CONTROLBUS...

Page 6: ...2 155 BURNER CONTROL THREADED MOUNTING HOLES 2 10 32 UNF 1 25 FLAME ROD TARGET CERAMIC INSULATORS IGNITION ELECTRODE Q179C ONLY BRACKET M1983 3 1 8 79 1 21 32 42 1 13 32 36 3 8 10 1 2 13 1 1 16 27 25...

Page 7: ...11 BSP P1 INTERNAL THREADS DIN APPROVED C7035A1064 HAS 1 2 14 BSP F INTERNAL THREADS MODEL AVAILABLE WITH 12 FOOT 3 66 METER LEADWIRES 2 3 INSERTION DEPTH 6 FOOT 1 83 METER LEADWIRES 2 3 M1945A 2 5 8...

Page 8: ...nal system fault occurred c Main valve terminal is not energized d No flame present and configuration jumper is selected for lockout e Pilot valve terminal is not energized SAFETY PROVISIONS Internal...

Page 9: ...tinually through STANDBY to detect any possibility of a runaway detector or a flame If a flame exists a safety shutdown occurs A standard amplifier is energized continually through STANDBY if a flame...

Page 10: ...f part 15 of FCC rules which are designed to provide reasonable protection against such interference when operated in a commercial environment Operation of this equipment in a residential area is like...

Page 11: ...must be capable of conducting the current to blow the 20A fuse or breaker in event of an internal short circuit The 7890 needs a low impedance ground connection to the equipment frame which in turn n...

Page 12: ...AY TO SWITCH THE F LEAD THE RELAY MUST HAVE GOLD CLAD OR GOLD FLASH CONTACTS AND A 120 VAC COIL POWER THE RELAY COIL FROM THE Q7800 SUBBASE TERMINAL 8 CONNECT THE RELAY CONTACTS BETWEEN THE F LEAD OF...

Page 13: ...ION TRANSFORMER MAIN VALVE 1 Q7800 2 2 3 3 5 4 L2 FOR A CONTINUOUS OR STANDING PILOT INSTALL AN EXTERNAL RELAY TO SWITCH THE F LEAD THE RELAY MUST HAVE GOLD CLAD OR GOLD FLASH CONTACTS AND A 230 VAC C...

Page 14: ...for electrical signal voltage probes 3 Make sure no subbase wiring is projecting beyond the terminal blocks Tuck in wiring against the back of the subbase so it does not interfere with the knife blad...

Page 15: ...required checkout tests Installing The Flame Detector NOTE Table 2 and Fig 13 list the flame detection systems available for use with the 7890 Make sure the correct combination of amplifier and flame...

Page 16: ...b 2a EARTH GROUND C7076A OR C7076D TERMINAL BLOCK L2 COMMON L1 HOT G F X X FLAME ROD G F X X PHOTOCELL 1 FLAME DETECTOR LEADS ARE COLOR CODED THE BLUE LEAD MUST BE CONNECTED TO THE F TERMINAL AND THE...

Page 17: ...Up Safe Start Check The 7890 verifies that a flame does not exist and proceeds into the Ignition Trial If a flame is present the 7890 will recycle to the STANDBY period If the critical loads are not i...

Page 18: ...a jumper on the subbase 3 Before continuing to the next test be sure to remove the test jumper s used in the previous tests 4 Replace all limits and interlocks not operating properly Do not bypass lim...

Page 19: ...mper s WARNING Make sure all manual fuel shutoff valves are closed MPORTANT Low fuel pressure limits if used can be open Bypass them with jumpers for the remaining Static tests if required Table 4 Sta...

Page 20: ...mum sensitivity 0 300 Vac capability 0 6000 ohm capability 0 10 Vdc capability Checkout Summary Preliminary inspection all installations Flame signal measurement all installations Initial lightoff che...

Page 21: ...the peaks and valleys caused by the self checking operation 6 The meter reading must be as specified in Table 5 after all tests are completed and all adjustments are made As an option the flame signal...

Page 22: ...on the subbase and close the master switch and return to step 4 7 When the pilot ignites measure the flame signal If the pilot flame signal is unsteady or approaching the 1 25 Vdc minimum value adjus...

Page 23: ...for flame stability and input rating If a second stage is used proceed to step 18 P Shut down the system by opening the burner switch or by lowering the setpoint of the operating controller Make sure...

Page 24: ...itches L Run the system through another cycle to check for normal operation M Return the system to normal operation Ignition Interference Test All Flame Rods Test to be sure that a false signal from a...

Page 25: ...or Ignition Spark Response Test All Ultraviolet Detectors Test to be sure that the ignition spark is not actuating the FLAME LED 1 Close the pilot and main burner manual fuel shutoff valve s 2 Start t...

Page 26: ...uence status messages indicating INITIATE STANDBY SAFE START CHECK PILOT IGN and RUN The selectable messages also provide visual indication current status and historical status of the equipment such a...

Page 27: ...line voltage is at a sufficient level for proper operating parameters STANDBY The LED indicates the burner status POWER The burner can be placed in STANDBY by opening the burner switch or if the opera...

Page 28: ...Wanchai Hong Kong Home and Building Control Honeywell Limited Honeywell Limit e 155 Gordon Baker Road North York Ontario M2H 2C9 Honeywell Latin American Division Miami Lakes Headquarters 14505 Comme...

Reviews: