background image

7800 SERIES EC7890A,B/RM7890A,B RELAY MODULE

65-0204–1

24

6

After the sequence has entered the normal burner run
period, turn down the pilot gas pressure very slowly,
reading the manometer (or gauge) as the pressure
drops. Stop immediately when the FLAME LED goes
out. Note the pressure at this point.

NOTE:

If there is no flame present for the selected
Flame Failure Response Test (FFRT), the
7890 will lock out.

a.

If the Flame Failure Action jumper (see Table 3,
JR2)

 is not clipped, allow the 7890A,B to recycle

to PILOT IGNITION. If the Flame Failure Action
jumper 

is clipped, push the reset pushbutton and

allow the 7890A,B to recycle to PILOT IGNITION.

b.

As the control attempts to relight the pilot,
increase the pilot pressure immediately until the
FLAME LED comes on, and then turn it down
slowly to obtain a pressure reading just above the
dropout point or until the flame signal increases
to approximately 1.25 Vdc. This step must be
completed within four or ten seconds, depending
on the selected PFEP, or lockout will occur.

c.

Turn the pilot back down slightly but not enough
to cause the FLAME LED to go out. (Keep the
pilot gas pressure just above the reading noted in
step 6 above.)

NOTE:

Step d requires two people, one to open the
manual main fuel valve(s) and one to watch
for ignition.

d.

With the sequence in the normal burner run
mode, make sure that the automatic main fuel
valve(s) is open. Smoothly open the manual
main fuel shutoff valve(s) and watch for main
burner lightoff.

e.

If the main flame is not established within five
seconds or the normal lightoff period specified by
the burner manufacturer, close the manual main
fuel shutoff valve(s) and open the master switch.
Then return to step 6a. If the burner flame is
established in the normal lightoff period, proceed
to step 10.

7

Recycle the burner and let the sequence advance to
the PILOT IGN period.

8

Increase the pilot flame size by increasing its fuel flow
until a smooth main flame is accomplished.

9

Reposition the flame scanner sight tube or use orifices
until the pilot flame signal voltage is approximately 1.25
to 1.50 Vdc.

J

When the main burner lights reliably with the pilot at
turndown, disconnect the manometer (or pressure
gauge) and turn the pilot gas flow up to that
recommended by the equipment manufacturer.

K

If used, remove the bypass jumpers from the subbase
terminals, limits/control or switches.

L

Run the system through another cycle to check for
normal operation.

M

Return the system to normal operation.

Ignition Interference Test (All Flame Rods)

Test to be sure that a false signal from a spark ignition system
is not superimposed on the flame signal.

Ignition interference can subtract from (decrease) or add to
(increase) the flame signal. If it decreases the flame signal
enough, it will cause a safety shutdown. If it increases the
flame signal, it could cause the FLAME LED to come on when
the true flame signal is below the minimum acceptable value.

Start the burner and measure the flame signal with both
ignition and pilot (or main burner) on, and then with only the
pilot (or main burner) on. Any significant difference (greater
than .5 Vdc) indicates ignition interference.

To Eliminate Ignition Interference

1

Make sure there is enough ground area.

2

Be sure the ignition electrode and the flame rod are on
opposite sides of the ground area.

3

Check for correct spacing on the ignition electrode:

a.

6,000V systems - 1/16 to 3/32 in. (1.6 to 2.4 mm).

b.

10,000V systems - 1/8 in. (3.2 mm).

4

Make sure the leadwires from the flame rod and ignition
electrode are not too close together.

5

Replace any deteriorated leadwires.

6

If the problem cannot be eliminated, the system may
have to be changed to an ultraviolet or infrared flame
detection system.

Hot Refractory Saturation Test
(All Infrared Detectors)

Test to be sure that radiation from hot refractory does not
mask the flickering radiation of the flame itself.

Start the burner and monitor the flame signal during the
warm-up period. A decrease in signal strength as the
refractory heats up indicates hot refractory saturation. If
saturation is extreme, the flame signal will drop below
1.25 Vdc and the system will shut down as though a flame
failure has occurred.

If hot refractory saturation occurs, the condition must be
corrected. Add an orifice plate in front of the cell to restrict the
viewing area; try to lengthen the sight pipe or decrease the
pipe size (diameter). Continue adjustments until hot refractory
saturation is eliminated.

Hot Refractory Hold-In Test (Rectifying
Photocell or All Infrared Detectors)

Test to be sure hot refractory will not delay the flame
detection system response to a flameout. This condition can
delay response to flame failure and also can prevent a
system restart as long as hot refractory is detected.

To check rectifying photocells for hot refractory hold-in,
operate the burner until the refractory reaches its maximum
temperature. Then terminate the firing cycle by lowering the

Summary of Contents for 7800 Series

Page 1: ...umpers GENERAL The Yamatake Honeywell EC7890A B RM7890A B is a micro processor based integrated burner control for automatically fired gas oil or combination fuel single burner applications Except whe...

Page 2: ...onnection between the subbase and the control panel or the equipment The earth ground wire must be capable of conducting the current to blow the 20A fuse or breaker in event of an internal short circu...

Page 3: ...urface corrosion 2 Range of allowable operating frequencies is 45 to 66 Hz 3 2000 VA maximum connected load to 7890 Assembly Environmental Ratings Ambient Temperature Operating 40 F to 140 F Storage 6...

Page 4: ...er if the detection system fails h When an R7861A is used with an EC7890B the application requires the use of a step down transformer See Fig 14 Plug in Flame Signal Amplifiers Applicable Flame Detect...

Page 5: ...NAGER part no ZM7850A1001 Network Interface Unit part no Q7700B1004 Communication Interface ControlBus Module part no QS7800A1001 ControlBus 5 Wire Electrical Connector part no 203541 DATA CONTROLBUS...

Page 6: ...2 155 BURNER CONTROL THREADED MOUNTING HOLES 2 10 32 UNF 1 25 FLAME ROD TARGET CERAMIC INSULATORS IGNITION ELECTRODE Q179C ONLY BRACKET M1983 3 1 8 79 1 21 32 42 1 13 32 36 3 8 10 1 2 13 1 1 16 27 25...

Page 7: ...11 BSP P1 INTERNAL THREADS DIN APPROVED C7035A1064 HAS 1 2 14 BSP F INTERNAL THREADS MODEL AVAILABLE WITH 12 FOOT 3 66 METER LEADWIRES 2 3 INSERTION DEPTH 6 FOOT 1 83 METER LEADWIRES 2 3 M1945A 2 5 8...

Page 8: ...nal system fault occurred c Main valve terminal is not energized d No flame present and configuration jumper is selected for lockout e Pilot valve terminal is not energized SAFETY PROVISIONS Internal...

Page 9: ...tinually through STANDBY to detect any possibility of a runaway detector or a flame If a flame exists a safety shutdown occurs A standard amplifier is energized continually through STANDBY if a flame...

Page 10: ...f part 15 of FCC rules which are designed to provide reasonable protection against such interference when operated in a commercial environment Operation of this equipment in a residential area is like...

Page 11: ...must be capable of conducting the current to blow the 20A fuse or breaker in event of an internal short circuit The 7890 needs a low impedance ground connection to the equipment frame which in turn n...

Page 12: ...AY TO SWITCH THE F LEAD THE RELAY MUST HAVE GOLD CLAD OR GOLD FLASH CONTACTS AND A 120 VAC COIL POWER THE RELAY COIL FROM THE Q7800 SUBBASE TERMINAL 8 CONNECT THE RELAY CONTACTS BETWEEN THE F LEAD OF...

Page 13: ...ION TRANSFORMER MAIN VALVE 1 Q7800 2 2 3 3 5 4 L2 FOR A CONTINUOUS OR STANDING PILOT INSTALL AN EXTERNAL RELAY TO SWITCH THE F LEAD THE RELAY MUST HAVE GOLD CLAD OR GOLD FLASH CONTACTS AND A 230 VAC C...

Page 14: ...for electrical signal voltage probes 3 Make sure no subbase wiring is projecting beyond the terminal blocks Tuck in wiring against the back of the subbase so it does not interfere with the knife blad...

Page 15: ...required checkout tests Installing The Flame Detector NOTE Table 2 and Fig 13 list the flame detection systems available for use with the 7890 Make sure the correct combination of amplifier and flame...

Page 16: ...b 2a EARTH GROUND C7076A OR C7076D TERMINAL BLOCK L2 COMMON L1 HOT G F X X FLAME ROD G F X X PHOTOCELL 1 FLAME DETECTOR LEADS ARE COLOR CODED THE BLUE LEAD MUST BE CONNECTED TO THE F TERMINAL AND THE...

Page 17: ...Up Safe Start Check The 7890 verifies that a flame does not exist and proceeds into the Ignition Trial If a flame is present the 7890 will recycle to the STANDBY period If the critical loads are not i...

Page 18: ...a jumper on the subbase 3 Before continuing to the next test be sure to remove the test jumper s used in the previous tests 4 Replace all limits and interlocks not operating properly Do not bypass lim...

Page 19: ...mper s WARNING Make sure all manual fuel shutoff valves are closed MPORTANT Low fuel pressure limits if used can be open Bypass them with jumpers for the remaining Static tests if required Table 4 Sta...

Page 20: ...mum sensitivity 0 300 Vac capability 0 6000 ohm capability 0 10 Vdc capability Checkout Summary Preliminary inspection all installations Flame signal measurement all installations Initial lightoff che...

Page 21: ...the peaks and valleys caused by the self checking operation 6 The meter reading must be as specified in Table 5 after all tests are completed and all adjustments are made As an option the flame signal...

Page 22: ...on the subbase and close the master switch and return to step 4 7 When the pilot ignites measure the flame signal If the pilot flame signal is unsteady or approaching the 1 25 Vdc minimum value adjus...

Page 23: ...for flame stability and input rating If a second stage is used proceed to step 18 P Shut down the system by opening the burner switch or by lowering the setpoint of the operating controller Make sure...

Page 24: ...itches L Run the system through another cycle to check for normal operation M Return the system to normal operation Ignition Interference Test All Flame Rods Test to be sure that a false signal from a...

Page 25: ...or Ignition Spark Response Test All Ultraviolet Detectors Test to be sure that the ignition spark is not actuating the FLAME LED 1 Close the pilot and main burner manual fuel shutoff valve s 2 Start t...

Page 26: ...uence status messages indicating INITIATE STANDBY SAFE START CHECK PILOT IGN and RUN The selectable messages also provide visual indication current status and historical status of the equipment such a...

Page 27: ...line voltage is at a sufficient level for proper operating parameters STANDBY The LED indicates the burner status POWER The burner can be placed in STANDBY by opening the burner switch or if the opera...

Page 28: ...Wanchai Hong Kong Home and Building Control Honeywell Limited Honeywell Limit e 155 Gordon Baker Road North York Ontario M2H 2C9 Honeywell Latin American Division Miami Lakes Headquarters 14505 Comme...

Reviews: