Heat / Cooling Meters Calculator Unit  

PolluTherm can be combined with PolluFlow 

Installation and Operating Instruction 

 

 
MH 6114 INT PolluTherm, Page 8 

When connecting in the four-wire system, the 
procedure is similar (refer to Figure 

15 and 

Section 11). 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 15: Example of connecting an unshielded 

cable in the four-wire system 

7. Display Options 

 
The different types of display options of the 
PolluTherm are in six levels. The displays 
indicated by (*) are hidden in the standard version 
and can be displayed depending on the setting of 
the meter. As required, the mask can be changed 
through the optical data interface by using the 
service software MiniCom Version 3.6.0.65. In 
default setting, the display switches on for one 
second at an interval of 4 seconds and indicates 
the cumulated heating energy. By pressing the 
red button, the first position displayed is activated 
in the User Level (cumulated heating energy). The 
other five levels can be accessed by pressing the 
red button for 8 seconds. The selection menu 
appears L1 to L6: 
 

 

User level 
 

 

Due Date level 

 

Archive level 

 

Service level 

 

Control level for 
tariff purposes 

 

Parameterization level 

 
 
By pressing the red button, the levels can be 
selected in the above sequence. When the 
required level is indicated, in order to attain this 
level, press the red button for 2 seconds. The 
individual display positions at the levels are called 
up consecutively by a momentarily pressing the 
button. If the button is not activated for approx. 4 
minutes, the display automatically returns to 
default. In all levels, volume pulses received are 
indicated by a flashing impeller symbol (left, lower 
corner of the display). 
 

7.1 User Level (Example) 

 

 

Error message 
(only for a pending error) 

 

Cumulated heating and 
cooling energy 

 

Consumption at the due 
date with associated date 

 

Cumulated volume 

 

Segment test 

 

Pulse value of the flow 
sensor 

 

Tariff consumption 1 * 
(if activated) 

 

Tariff consumption 
cooling * 
(if activated) 

 

Consumption of the 
external meter * 

 

Consumption of the 
second external meter * 

 

Actual flow 

Cable-tie for 
strain relief 

Summary of Contents for SENSUS PolluTherm

Page 1: ...ing Meters Calculator Unit PolluTherm can be combined with PolluFlow Installation and Operating Instructions MH 6114 INT PolluTherm Page 1 PolluTherm PolluFlow compatible Installation and Operating In...

Page 2: ...ule for M Bus slot 14 10 6 LONWORKS FTT10A 14 10 7 Inserting the Plug In Modules into the Calculator Unit 14 10 8 Combined Heat Cooling Meter Order Option 14 10 9 Optional Integrated Data Logger Order...

Page 3: ...Discharged batteries electronic devices or components that are no longer required must be disposed of as hazardous waste at suitable collection points If multiple meters are used in a billing unit sim...

Page 4: ...sensor should be installed in the heating flow or the warm pipe The direction of flow is indicated by an arrow on the housing The permitted operating pressure and operating temperature must not be exc...

Page 5: ...7 5 They are supplied up to R1 DN 25 The EN 1434 2 can be used as a general installation guideline When using Sensus temperature sensors with the installation lengths of 100 mm and 150 mm the active m...

Page 6: ...blish strain relief using a cable tie Figure 9 The pulse line white is connected to the terminal 10 and the line GND blue connected to the terminal 11 The terminal 9 is provided for the voltage supply...

Page 7: ...ollowing allocation applies Supply temperature sensor warm pipe Type of connection Terminals Two wire system 5 6 Four wire system 5 6 and 1 2 Pos available shielding Return temperature sensor cooling...

Page 8: ...ive levels can be accessed by pressing the red button for 8 seconds The selection menu appears L1 to L6 User level Due Date level Archive level Service level Control level for tariff purposes Paramete...

Page 9: ...ting 0 Secondary M Bus address Factory setting Serial number 7 2 Due date Level Example All display positions are indicated by an arrow Display of all values are saved to an adjustable due date in the...

Page 10: ...the second external meter Maximum flow in the selected month with date averaged Maximum flow in the selected month with time averaged Maximum energy in the selected month with date averaged Maximum e...

Page 11: ...point for inlet flow temperature cooling metering if activated Switching point for outlet temperature difference cooling metering if activated Correction factor for water frost protection mixture if a...

Page 12: ...n point of the temperature sensors Cover of the calculator unit pull lockwire through the eyelet at the bottom edge 9 Possible Error Situations PolluTherm is equipped with an automatic self monitoring...

Page 13: ...g The primary address can be set at between 0 and 250 and when delivered factory default is set at 0 Battery devices have an M Bus credit as such the daily read out is limited depending on the number...

Page 14: ...omatic switching point The factory setting for switching to cooling metering is Flow temperature 25 C and Negative temperature differential 0 15 K To switch back to warm metering the following applies...

Page 15: ...able for the temperature sensors can be extended to a maximum of approx 23 m In order to compensate for the additional cable resistance the so called four wire system is used Cable with four wires is...

Page 16: ...Heat Cooling Meters Calculator Unit PolluTherm can be combined with PolluFlow Installation and Operating Instruction MH 6114 INT PolluTherm Page 16...

Page 17: ...Heat Cooling Meters Calculator Unit PolluTherm can be combined with PolluFlow Installation and Operating Instructions MH 6114 INT PolluTherm Page 17...

Page 18: ...Heat Cooling Meters Calculator Unit PolluTherm can be combined with PolluFlow Installation and Operating Instruction MH 6114 INT PolluTherm Page 18...

Page 19: ...Heat Cooling Meters Calculator Unit PolluTherm can be combined with PolluFlow Installation and Operating Instructions MH 6114 INT PolluTherm Page 19...

Page 20: ...tallation and Operating Instruction MH 6114 INT PolluTherm Page 20 Material number 28505234 Version 10 2021 0007 subject to modifications Sensus GmbH Ludwigshafen Industriestra e 16 D 67063 Ludwigshaf...

Reviews: