Heat / Cooling Meters Calculator Unit  

PolluTherm can be combined with PolluFlow 

Installation and Operating Instruction 

 

 
MH 6114 INT PolluTherm, Page 2 

The calculator unit PolluTherm is used for energy 
consumption measurement in heating or cooling 
systems, with water as the energy-carrying 
medium. For applications with frost protection 
additive in water, it is only possible to use 
PolluTherm as uncalibrated non-MID conformed 
device, and the correction factor for the K-factor in 
this case can be programmed. This manual 
describes the installation and operation of the 
calculator unit PolluTherm. It contains important 
information that shall be read by the end user of 
this product 
 
 

Contents 

 
1. Technical Data .................................................. 2

 

3. Tools Required ................................................. 3

 

4. Combination of the Sub-assemblies ................. 3

 

5.1 Flow Sensor PolluFlow ............................... 4

 

5.2 Installation of the Temperature Sensor ....... 5

 

5.3 Installation of the Calculator Unit ................ 5

 

6. Connection of the Sub-Assemblies .................. 6

 

6.1 Connecting the Flow Sensor ....................... 6

 

Table 10: Connection diagram .......................... 7

 

6.2 Connecting the Temperature Sensor .......... 7

 

7. Display Options ................................................. 8

 

7.1 User Level (Example) ................................. 8

 

7.2 Due date Level (Example) .......................... 9

 

7.3 Archive Level (Example) ........................... 10

 

7.4. Service Level (Example) .......................... 10

 

7.5 Control Level for Tariff Purposes (Example)
 ........................................................................ 11

 

7.6 Parameterization Level (Example) ............ 11

 

8. Function Check, Sealing ................................. 12

 

9. Possible Error Situations ................................ 12

 

10. Data Interfaces and Options ......................... 13

 

10.1 Optical Interface ...................................... 13

 

10.2 M-Bus Plug-In Module acc. to EN 13757-3
 ........................................................................ 13

 

10.3 Telecounting Plug-In Module .................. 13

 

10.4 M-Bus Plug-In Module with Two Pulsed 
Inputs .............................................................. 13

 

10.5 USB Plug-In Module (for M-Bus slot) ...... 14

 

10.6 LONWORKS

®

-FTT10A ........................... 14

 

10.7 Inserting the Plug-In Modules into the 
Calculator Unit ................................................. 14

 

10.8 Combined Heat / Cooling Meter (Order 
Option) ............................................................ 14

 

10.9 Optional Integrated Data Logger (Order 
Option) ............................................................ 14

 

10.10 Conversion of Battery Device to Power 
Supply Device ................................................. 14

 

11. Note for Extending the Temperature Sensor 
Cables ................................................................. 15

 

 

 
 
 

 

What is Included in the packaging: 

 

  Calculator unit PolluTherm (possibly with 

temperature sensors and sleeves or ball 
valve) 

 

  Sealing material (self-lock seals, locking 

wire), cable-ties for strain relief 

 

  Attachment material (2 screws,  

2 dowels, C-rails) 

 

  Installation and Operating Instruction 

 

1. Technical Data 

 

Calculator unit 

Temperature measurement 
range 

  

 = 1 … 180 °C 

Temperature differential 
range 

 = 3 … 150 K 

Switch-off limit 

0.15 K 

Measurement accuracy 

Better than (%): 
± (0.5 + 

min

 / 

Updating time or 
calculating cycles: 
- Temperature 
- Flow, output 
- Energy, volume 
 

 
 
2 sec 
4 sec 
4 sec (16 sec *) 
* for battery operation 

Optical data interface 

Physical according to EN 
61107 
Data telegram according to 
EN 13757-3 

Suitable temperature 
sensor 

Pt 500 
Connection in two or four-wire 
system 

Power supply 
 
(there is the respective 
calibration period) 

Battery for 6 years 
(optional: 11 years) 
or power supply 230 V AC or 
24 V AC 

Electromagnetic 
environmental condition 

Class E 1 

Mechanical environmental 
condition 

Class M 2 

Protection class 

IP 54 

Ambient temperature 

5 … 55 °C 

Storage temperature 

-20 … +65 °C 

Relative air humidity 

< 93 % 

Size (H x W x D) 
regarding wall installation 

approx. 159 x 125 x 52 mm 

 
 
 
 
 
 
 
 
 
 
 
 
 

Input 

pulse value 

in l 

 

 

10 

Display of the 

calculator unit with 

decimal points for m³, 

MWh or GJ 

00000.000 000000.00 

Pulse value 

for telecounting 

of the heat quantity in 

MWh or GJ 

0.001 0.01 

Pulse value 

for telecounting 

of the volume in l 

1 10 

Summary of Contents for SENSUS PolluTherm

Page 1: ...ing Meters Calculator Unit PolluTherm can be combined with PolluFlow Installation and Operating Instructions MH 6114 INT PolluTherm Page 1 PolluTherm PolluFlow compatible Installation and Operating In...

Page 2: ...ule for M Bus slot 14 10 6 LONWORKS FTT10A 14 10 7 Inserting the Plug In Modules into the Calculator Unit 14 10 8 Combined Heat Cooling Meter Order Option 14 10 9 Optional Integrated Data Logger Order...

Page 3: ...Discharged batteries electronic devices or components that are no longer required must be disposed of as hazardous waste at suitable collection points If multiple meters are used in a billing unit sim...

Page 4: ...sensor should be installed in the heating flow or the warm pipe The direction of flow is indicated by an arrow on the housing The permitted operating pressure and operating temperature must not be exc...

Page 5: ...7 5 They are supplied up to R1 DN 25 The EN 1434 2 can be used as a general installation guideline When using Sensus temperature sensors with the installation lengths of 100 mm and 150 mm the active m...

Page 6: ...blish strain relief using a cable tie Figure 9 The pulse line white is connected to the terminal 10 and the line GND blue connected to the terminal 11 The terminal 9 is provided for the voltage supply...

Page 7: ...ollowing allocation applies Supply temperature sensor warm pipe Type of connection Terminals Two wire system 5 6 Four wire system 5 6 and 1 2 Pos available shielding Return temperature sensor cooling...

Page 8: ...ive levels can be accessed by pressing the red button for 8 seconds The selection menu appears L1 to L6 User level Due Date level Archive level Service level Control level for tariff purposes Paramete...

Page 9: ...ting 0 Secondary M Bus address Factory setting Serial number 7 2 Due date Level Example All display positions are indicated by an arrow Display of all values are saved to an adjustable due date in the...

Page 10: ...the second external meter Maximum flow in the selected month with date averaged Maximum flow in the selected month with time averaged Maximum energy in the selected month with date averaged Maximum e...

Page 11: ...point for inlet flow temperature cooling metering if activated Switching point for outlet temperature difference cooling metering if activated Correction factor for water frost protection mixture if a...

Page 12: ...n point of the temperature sensors Cover of the calculator unit pull lockwire through the eyelet at the bottom edge 9 Possible Error Situations PolluTherm is equipped with an automatic self monitoring...

Page 13: ...g The primary address can be set at between 0 and 250 and when delivered factory default is set at 0 Battery devices have an M Bus credit as such the daily read out is limited depending on the number...

Page 14: ...omatic switching point The factory setting for switching to cooling metering is Flow temperature 25 C and Negative temperature differential 0 15 K To switch back to warm metering the following applies...

Page 15: ...able for the temperature sensors can be extended to a maximum of approx 23 m In order to compensate for the additional cable resistance the so called four wire system is used Cable with four wires is...

Page 16: ...Heat Cooling Meters Calculator Unit PolluTherm can be combined with PolluFlow Installation and Operating Instruction MH 6114 INT PolluTherm Page 16...

Page 17: ...Heat Cooling Meters Calculator Unit PolluTherm can be combined with PolluFlow Installation and Operating Instructions MH 6114 INT PolluTherm Page 17...

Page 18: ...Heat Cooling Meters Calculator Unit PolluTherm can be combined with PolluFlow Installation and Operating Instruction MH 6114 INT PolluTherm Page 18...

Page 19: ...Heat Cooling Meters Calculator Unit PolluTherm can be combined with PolluFlow Installation and Operating Instructions MH 6114 INT PolluTherm Page 19...

Page 20: ...tallation and Operating Instruction MH 6114 INT PolluTherm Page 20 Material number 28505234 Version 10 2021 0007 subject to modifications Sensus GmbH Ludwigshafen Industriestra e 16 D 67063 Ludwigshaf...

Reviews: