5.2 Start-up and Initial Programming
Refer to
on page 16 for an explanation of the buttons on the user
interface.
1. Check that all the electrical, mechanical, and hydraulic connections have been made.
on page 13.
2. Turn on the power to the controller.
– All the LEDs (7) (8) (9) (10) turn on and, if there are no faults, turn off again within
10 seconds.
– The controller performs an autotest and the Power LED (7) turns on.
– The display shows the software version.
NOTICE:
– The controller enters MANUAL mode upon initial start-up. The mode at power-up is
the same one the controller was in when it was previously turned off.
– After turning off power to the controller, wait a minimum of 20 seconds before
applying power. This procedure is to prevent the risk of internal damage to the
controller.
3. Enter the BASIC MENU to set the pressure setting.
– If the controller is not in MANUAL Mode, switch to MANUAL mode by pressing (2)
; in MANUAL mode the Mode LED (10) is off.
–
In MANUAL mode, press and hold (3)
for 3 seconds until the first parameter to
be edited appears on the display and the Mode LED (10) flashes.
– The display toggles between
A
(Motor Current setting) and a number. Make sure
that the number matches the current rating on the motor nameplate. This value is
preset from the factory for packaged systems. Press (4)
or (5)
to change
the value of the parameter, then press (6)
to save the setting and select the
next parameter.
–
Press (6)
until the Pressure Setpoint (
SP
) is reached. Press (4)
or (5)
to edit the Pressure Setpoint, then press (6)
to save the setting.
–
Press (6)
until the Pressure Drop (
dP
) is reached. When in Standby mode, the
controller starts the pump when the system pressure is less than the Pressure Drop
value. Set the Pressure Drop value as a percentage of the Pressure Setpoint. For
example, if the Pressure Setpoint is 50 psi and the desired pressure drop is 5 psi,
set the
dP
value to 90. Press (4)
or (5)
to edit, press (6)
to save.
–
Press (3)
to exit the BASIC MENU.
–
Press (1)
to enter AUTOMATIC Mode and Mode LED (10) is steady green.
5 System Description
ResiBoost INSTRUCTION MANUAL
17