6 Alarms
6.1 Alarms and warnings
Refer to
on page 16 for an explanation of the buttons on the user
interface.
When an alarm is triggered or the controller is locked, the fault LED (8) is illuminated and
steady and the pump is stopped.
WARNING:
If the controller is in AUTOMATIC mode and is turned off and on again, it will power up in
AUTOMATIC mode and can start the pump.
The last alarm is shown on the display. It is possible for several alarms to be triggered at
the same time.
Manual Alarm reset
To manually reset an alarm and start the pump:
1.
Press (2)
to enter MANUAL mode.
2.
Press (4)
or (5)
to view the types of alarms in progress, if there is more than
one.
3. Eliminate the cause of the alarms.
4.
Press (6)
to reset the alarms. The Error LED (8) will turn off when the alarm is reset.
5.
Press (1)
to return to AUTOMATIC mode. The controller will then operate the
pump based on settings and system conditions.
WARNING:
• Alarm
A1
(No Water) and
A4
(Minimum Pressure) are not available in MANUAL mode.
In MANUAL mode it is possible to run the pump without protection.
• Alarms
A2
,
A3
,
A5
,
A6
,
A7
,
A8
,
A9
are available in MANUAL mode and when an alarm is
triggered, the Error LED (8) is illuminated and the pump cannot be started by pressing
(2)
.
6 Alarms
24
ResiBoost INSTRUCTION MANUAL