Press (2)
to enter MANUAL mode.
•
Press and hold (3)
for 3 seconds to access The BASIC MENU (MB). The Mode LED
(10) flashes.
•
Press (4)
or (5)
to edit the value of the parameter.
• The parameters will be displayed in the sequence shown in the following table.
•
Press (6)
to save and move on to the next parameter.
•
The menu will exit after the last parameter or if (3)
is pressed. The Mode LED (10)
turns off after exiting the menu.
Table 4: MB Parameter description
Parameter
Description
Range
Unit
Default
A
Motor Current Setting - Set
the current rating to the
value on the motor
nameplate.
4
WARNING: If the Motor
Current Setting is not
configured correctly, the
motor might NOT be
protected against overload
and which can result in
damage.
0.1–Imax
Ampere
Imax
5
FL
Minimum Frequency – start
and stop frequency of the
motor. In AUTOMATIC
mode, the controller stops
the pump and enters
standby when the
minimum frequency is
reached.
20–45 (RB1)
15–45 (RB3)
Hz
30
EL
Enable for the Low water
digital input - Connect a
non-powered switch to the
input, for example a
pressure or float switch.
Alarm
A1
(No Water) will
be issued if parameter
EL
=1 and the switch is open.
0: Disabled, no control
1: Enabled
-
0
SP
Pressure Setpoint – target
value for pressure control.
7.25 - 85
PSI
60
4
Imax: maximum current supplied. The value varies according to the model of controller.
5 System Description
20
ResiBoost INSTRUCTION MANUAL