8.4.2 Pump control
Part
Default value
Values
Description
Pump name
–
Four or more
characters
The option to change the name of the
pump
Site name
–
Four or more
characters
The option to change the name of the
site
Start condition
Timer
• Timer
• Float
• Timer/Float
The selection of the start condition of the
automatic control mode
Stop condition
Snore
• Snore
• Float
The selection of the stop condition of the
automatic control mode
Only the stop conditions that are
applicable for the configured start
condition are shown.
Snoring sensitivity 0.86
0–1
Low value
High value
The snoring
sensitivity is low.
Snoring is detected
at high air volumes
in the fluid.
The snoring
sensitivity is high.
Snoring is detected
at low air volumes
in the fluid.
Level settings
1
1–10
The value of the Level settings
parameter is used to calculate the pause
time. The parameter does not define the
water level in the well.
Minimum pause
time
25 s
1–999 s
The minimum time that the pump is on
standby
Maximum pause
time
90 s
1–999 s
The maximum time that the pump is on
standby
Reference power
According to the
information from
the pump module
–
The value of the reference power
The controller uses the reference power
of the pump to detect snoring.
There are three options to set the
reference power:
• Reference power
• Calibrate the reference power
• Reset reference power
Correct the rotation –
–
The option to switch the pump rotation
Used when the pump has been
miswired.
The option can only be used in standard
mode.
8.4.3 Alarm
Alarm
Default value
Values
Description
Service alarm
Enabled
• Disabled
• Enabled
• Disabled
The alarm is disabled.
• Enabled
The alarm is enabled.
8 User Interface
DCM 711 Installation, Operation, and Maintenance Manual
39