5.3.8 Set the reference power
The controller uses the reference power of the pump to detect snoring. If the reference
power is not known, then the parameter is configured in the Settings menu.
Set the reference power.
Condition
Action
Use of the default
reference power.
1. Go to Settings > Pump control > Reference power > Reset reference
power.
2. Confirm.
Calibration of the
reference power.
1. Check that there is water in the well.
2. Press the HAND button.
3. Go to Settings > Pump control > Reference power > Calibrate the
reference power.
4. Confirm the initialization of the calibration.
Manual set of the
reference power.
1. Go to Settings > Pump control > Reference power > Reference power.
2. Type the value.
5 System Setup and Operation
26
DCM 711 Installation, Operation, and Maintenance Manual