Alarm
Default value
Values
Description
500 h
Interval
• 1–10000 h
The delay from the time
that the alarm is
triggered, until the alarm
is active again.
Motor overtemperature
Enabled
Reset required
• Disabled
• Enabled
• Disabled
The alarm resets
automatically.
• Enabled
The alarm must be
reset manually.
8.4.4 Communication settings
WLAN
Part
Default value
Values
Description
Enabled
Disabled
• Disabled
• Enabled
The option to enable or
disable WLAN
SSID
-
More than 4 characters
The name of the network
Password
-
More than 4 characters
The password of the
selected WLAN network
Local IP address
192.168.1.50
0.0.0.0-255.255.255.255
The settings for
communication by
Ethernet
Subnet mask
255.255.255.0
0.0.0.0-255.255.255.255
Default gateway
192.168.1.1
0.0.0.0-255.255.255.255
Regulatory domain
FCC
• FCC
• ETSI
• TELEC
The option to select the
regulatory domain
Modbus TCP
• Slave address
1
1–247
The settings for
communication by Modbus
TCP
Bluetooth
Part
Default value
Values
Description
Enabled
On
• On
• Off
The option to turn on or
turn off Bluetooth
Ethernet
Part
Default value
Values
Description
Local IP address
192.168.1.20
0.0.0.0-255.255.255.255
The settings for
communication by
Ethernet
Subnet mask
255.255.255.0
0.0.0.0-255.255.255.255
Default gateway
192.168.1.1
0.0.0.0-255.255.255.255
Modbus TCP
• Slave address
1
1–247
The settings for
communication by Modbus
TCP
RS-485
Modbus RTU
8 User Interface
40
DCM 711 Installation, Operation, and Maintenance Manual