Chapter 2 – Installation
Installation Overview
The design of the 5019T allows the unit to be installed in most industrial
environments. The system is generally placed in a NEMA 4/4X/12 enclosure
to protect against contaminants such as dust and moisture. Class II
Hazardous Locations always require a Type 12 (dust-proof) minimum
enclosure rating.
Read the following sections carefully to be sure that you are complying with
all the safety requirements.
1. Select a NEMA rated enclosure and place the unit within the enclosure to
allow easy access to the system ports (see other sections in this chapter and
Appendix A).
•
To assure a NEMA 4 seal, choose an approved enclosure that
has a 14-gauge (0.075 in/1.9 mm thick steel or 0.125 in/3.2 mm
thick aluminum) front face.
•
Be sure to account for the unit’s depth when choosing the depth of
the enclosure.
2. Create a cutout in the enclosure (see Figure 2-2).
3. Be sure to place the unit at a comfortable working level
4. Make sure the area around the cutout is clean and free from metal burrs
5. Mount the unit in an upright position and properly secure the unit into the
panel.
6. Attach one end of the power cord to the power receptacle on the unit and the
other end to a properly grounded 100-240 VAC, 50-60 Hz outlet, or optional
18-30 VDC power source.
•
When using the USB touch interface option, you must also attach
the ground strap cable to one of the three 6-32 mounting screws
on the back cover of the 5019 and connect the other end of the
cable to the Protective Earth ground.
7. Turn on power to the 5019T unit. Then turn on power to the host computer.
The system will boot up into the operating system.
8. Install the application software on the host computer via a floppy drive, CD-
ROM, or the network.