5015T Flat Panel Industrial Monitor Chapter 2 Installation
11
142029 (D)
Hazardous Locations Installations
Xycom Automation designed the systems with the intention of meeting the requirements
of Class I, Division 2 Hazardous Locations applications. Division 2 locations are those
locations that are normally non-hazardous, but potentially hazardous should an accident
expose the area to flammable vapors, gases or combustible dusts.
These systems are non-incendiary devices. They are not intrinsically safe and should never
be operated within a Division 1 (normally hazardous) location when installed as described
here. Nor should any peripheral interface device attached to these systems be located within
Division 1 locations unless approved and/or certified diode barriers are placed in series with
each individual signal and DC power line. Any such installations are beyond the bounds of
Xycom Automation design intent. Xycom Automation accepts no responsibility for
installations of this equipment or any devices attached to this equipment in Division 1
locations.
NOTE:
It is the customer’s responsibility when adding additional cards that they met operating
conditions for Class I, Division 2 hazardous locations.
It is the responsibility of the customer to ensure that the product is properly rated for the
location. If the intended location does not presently have a Class, Division, and Group
rating, then users should consult the appropriate authorities having jurisdiction in order to
determine the correct rating for that Hazardous Location.
In accordance with Federal, State/Provincial, and Local regulations, all hazardous
location installations should be inspected by the appropriate authority having jurisdiction
prior to use. Only technically qualified personnel should install, service, and inspect these
systems.
Warning
Suitable for use in Class I, Division 2 Groups A, B, C, and D, and Class II,
Division 2, Groups F and G hazardous locations or non-hazardous locations
only
.
Temperature Codes: T4A (5015T-24V), T4 (5015T)
Warning - Explosion Hazard
Substitution of components may impair suitability for Class I, Class II,
Division 2.
Advertissement Risque D’ Explosion
La substitution de composants peut rendre ce materiel inacceptable pour les
emplamements de classe I, II, Division 2.
Warning - Explosion Hazard
Do not disconnect equipment unless the power has been switched off or the
area is known to be non-hazardous.