VESDA by Xtralis
VESDA Pipe Network Design Guide
www.xtralis.com
13
4.4.3
Return Air Grille Sampling
The sampling pipe is placed over the return air grille of a duct or an Air Handling Unit (AHU). Figure 4-8
illustrates pipe mounting over the return air grille. The number of AHUs that can be covered by different
detectors is dependent on the suction power of the AHU and also on the size of the return air grille.
Recommendations:
l
a VESDA VLP or VESDA VLS detector should not monitor more than four AHUs
l
a VESDA VLC should not monitor more than two AHUs,
l
a VESDA VLF should not monitor more than one AHU.
l
the detectors should be in close proximity to the AHUs.
l
transport time should be less than 60 seconds.
l
sampling hole sensitivities should be maintained.
Legend
A
Sampling pipe
B
Return grill
C
End cap without hole
D
Sampling hole
Figure 4-8: Return air sampling over a return air grille
Note:
Socket unions are also used where it is important to have correct orientation of sampling holes.
4.4.4
Hot - Cold Aisle Sampling
In hot - cold aisle systems, the cabinets are adjoined into a series of rows, resting on a raised floor. The fronts
of the racks face each other and become cold aisles, due to the front-to-back heat dissipation of rack servers.
Hot - cold aisle protocol can be implemented with underfloor, overhead, horizontal displacement, or local air
distribution systems.
Figure 4-9: Hot - Cold Aisle System
l
Primary Sampling: Rear of racks, Air-return grills (CRAC, Ceiling)
l
Secondary Sampling: ceiling.
Summary of Contents for VESDA VLC-505
Page 1: ...VESDA Student Workbook Rev 8a 15SEP21 ...
Page 4: ...iv ...
Page 14: ...VESDA Course Overview 1 10 VESDA Student Workbook Create Xtralis Account ...
Page 20: ...VESDA Course Overview 1 16 VESDA Student Workbook ...
Page 23: ...VESDA Products VESDA Student Workbook 2 3 ASD iVESDA ASD ...
Page 24: ...VESDA Products 2 4 VESDA Student Workbook VESDA model comparison chart ...
Page 32: ...VESDA Products 2 12 VESDA Student Workbook Industrial facilities Industrial facilities ...
Page 33: ...VESDA Products VESDA Student Workbook 2 13 Solutions for all environments Detectors ...
Page 56: ...Installation 3 4 VESDA Student Workbook IDP Installation Practices ...
Page 68: ...Installation 3 16 VESDA Student Workbook ...
Page 74: ...VESDAnet Connection 4 6 VESDA Student Workbook ...
Page 218: ...VSC Software Installation A 4 VESDA Student Workbook ...
Page 224: ...ASPIRE Software Installation B 6 VESDA Student Workbook ...
Page 238: ...14 ...
Page 239: ...VESDA Pipe Network Design Guide February 2019 Document 10193_09 Part Number 30009 ...
Page 240: ......
Page 293: ...VESDA Pipe Network Installation Guide March 2019 Document 10255_08 Part Number 30008 ...
Page 294: ......
Page 333: ......
Page 334: ...VESDA Commissioning Guide December 2012 Document 10195_06 Part Number 30005 ...
Page 335: ......