VESDA Pipe Network Design Guide
VESDA by Xtralis
24
www.xtralis.com
4.10 Reference Sampling
Periodically, smoke and other pollutants from external sources may enter a protected zone temporarily raising
the smoke level. In this case the detector will detect the smoke and generate an alarm. Referencing is
employed to compensate for the periodic rise in smoke levels and to reduce nuisance alarms in high
sensitivity areas.
A separate VESDA detector is used to draw air from the external source and produce a reference reading of
the background level of smoke and pollutants. The reference reading is then subtracted from all VESDA
detectors monitoring the internal VESDA Addresses (also known as VESDA Zones). This allows the internal
VESDA detectors to determine if a rise in smoke levels is due to background pollution or a problem inside the
VESDA zone of protection. The ability to check the background level of smoke greatly reduces the chance of
detectors false alarming.
VESDA detectors in large installations typically operate at varying sensitivity levels. In such instances the
level of subtraction can be set differently for each detector.
Referencing is configured through Xtralis VSC, LCD Programmer or Xtralis VSM4 Software. Refer to the
respective manuals for details.
Legend
A
Internal detectors
D
Reference area (Car park, Loading bay etc.)
B
Reference detector
E
VESDAnet
C
Reference sample pipe
Figure 4-26: Reference sampling
Summary of Contents for VESDA VLC-505
Page 1: ...VESDA Student Workbook Rev 8a 15SEP21 ...
Page 4: ...iv ...
Page 14: ...VESDA Course Overview 1 10 VESDA Student Workbook Create Xtralis Account ...
Page 20: ...VESDA Course Overview 1 16 VESDA Student Workbook ...
Page 23: ...VESDA Products VESDA Student Workbook 2 3 ASD iVESDA ASD ...
Page 24: ...VESDA Products 2 4 VESDA Student Workbook VESDA model comparison chart ...
Page 32: ...VESDA Products 2 12 VESDA Student Workbook Industrial facilities Industrial facilities ...
Page 33: ...VESDA Products VESDA Student Workbook 2 13 Solutions for all environments Detectors ...
Page 56: ...Installation 3 4 VESDA Student Workbook IDP Installation Practices ...
Page 68: ...Installation 3 16 VESDA Student Workbook ...
Page 74: ...VESDAnet Connection 4 6 VESDA Student Workbook ...
Page 218: ...VSC Software Installation A 4 VESDA Student Workbook ...
Page 224: ...ASPIRE Software Installation B 6 VESDA Student Workbook ...
Page 238: ...14 ...
Page 239: ...VESDA Pipe Network Design Guide February 2019 Document 10193_09 Part Number 30009 ...
Page 240: ......
Page 293: ...VESDA Pipe Network Installation Guide March 2019 Document 10255_08 Part Number 30008 ...
Page 294: ......
Page 333: ......
Page 334: ...VESDA Commissioning Guide December 2012 Document 10195_06 Part Number 30005 ...
Page 335: ......