ASPIRE Software
VESDA Student Workbook
7-3
VEWFD
(Very Early Warning Fire Detection)
EWFD
(Early Warning Fire Detection)
SFD
(Standard Fire Detection)
Sensitivity at each port/ sensor
1.0% obs/ft.
1.5% obs/ft.
2.5% obs/ft.
Coverage
Open Area
200 sq. ft.
400 sq. ft.
900 sq. ft.
Return Air Grille
4 sq. ft. (Grille Area)
Duct Detection
Duct Detection
Transport Time
60 Seconds
90 Seconds
120 Seconds
• Detector sensitivity is determined by ASPIRE to be verified as per local codes.
• Smoke thresholds listed within the ASPIRE calculation are a guide only and are bound by a standard
range. Exact smoke thresholds setting are to be modified and made suitable for the environment in
which the detector in installed.
Example US:
NFPA 76
Designing, codes, and sensitivity classification
Aspirating Smoke Detection can provide VEWFD, EWFD or SFD detection capabilities to match or exceed minimum NFPA 76 requirements
SPE aggregate area > 2500 ft2(232 m2)
SPE aggregate area ≤ 2500 ft2(232 m2)
Signal-Processing Equipment (SPE)
Room/area detection
Raised floors with combustibles
– No common airflow above and below
Raised floors with combustibles - common airflow above and below
VEWFD
EWFD below floor
VEWFD above floor (room/area detection)
EWFD
EWFD
EWFD
Cable Entrance Facility
EWFD
EWFD
Power Areas/Equipment
EWFD
EWFD
Main Distribution Frame Area (MDF)
Room/area detection
Raised floors with combustibles
– No common airflow above and below
Raised floors with combustibles - common airflow above and below
VEWFD
EWFD below floor
VEWFD above floor (room/area detection)
EWFD
EWFD
EWFD
Standby Engine Area
Heat or flame detection
Heat or flame detection
Technical Support Areas (TSA)
TSA not part of telecommunications equipment area
TSA contiguous with SPE or MDF areas
TSA contiguous with power areas
TSA part of telecommunications equipment area when SPE area ≤232 m2 (2,500 ft2)
SFD per NFPA 72
VEWFD
EWFD
Not Applicable
SFD per NFPA 72
See below
See below
EWFD
HVAC Systems
If VEWFD is required for the space (see above) then provide VEWFD as noted in next column
VEWFD ports to monitor return air; VEWFD ports to
monitor returns of stand-alone packaged HVAC units
Not applicable
Designing and codes
Summary of Contents for VESDA VLC-505
Page 1: ...VESDA Student Workbook Rev 8a 15SEP21 ...
Page 4: ...iv ...
Page 14: ...VESDA Course Overview 1 10 VESDA Student Workbook Create Xtralis Account ...
Page 20: ...VESDA Course Overview 1 16 VESDA Student Workbook ...
Page 23: ...VESDA Products VESDA Student Workbook 2 3 ASD iVESDA ASD ...
Page 24: ...VESDA Products 2 4 VESDA Student Workbook VESDA model comparison chart ...
Page 32: ...VESDA Products 2 12 VESDA Student Workbook Industrial facilities Industrial facilities ...
Page 33: ...VESDA Products VESDA Student Workbook 2 13 Solutions for all environments Detectors ...
Page 56: ...Installation 3 4 VESDA Student Workbook IDP Installation Practices ...
Page 68: ...Installation 3 16 VESDA Student Workbook ...
Page 74: ...VESDAnet Connection 4 6 VESDA Student Workbook ...
Page 218: ...VSC Software Installation A 4 VESDA Student Workbook ...
Page 224: ...ASPIRE Software Installation B 6 VESDA Student Workbook ...
Page 238: ...14 ...
Page 239: ...VESDA Pipe Network Design Guide February 2019 Document 10193_09 Part Number 30009 ...
Page 240: ......
Page 293: ...VESDA Pipe Network Installation Guide March 2019 Document 10255_08 Part Number 30008 ...
Page 294: ......
Page 333: ......
Page 334: ...VESDA Commissioning Guide December 2012 Document 10195_06 Part Number 30005 ...
Page 335: ......